User Manual
Overview
Equipment combinations
2
A6V11545892_en--_a 13 | 146
Type of unit Product no.
Datasheet
*)
Electric actuator, DC 0…10 V (for
radiator valves)
SSA61.. 4893
Electric actuator, DC 0…10 V (for 2-
and 3-port valves/V..P45)
SSC61.. 4895
Electric actuator, DC 0…10 V (for small
valves 2.5 mm)
SSP61.. 4864
Electric actuator, DC 0…10 V (for small
valves 5.5 mm)
SSB61.. 4891
Electromotive actuator, DC 0…10 V (for
valves 5.5 mm)
SAS61.. 4581
Electrothermal actuator, AC 24 V, NC,
DC 0…10 V, 1 m
STA63 4884
Electrothermal actuator, AC 24 V, NO,
DC 0…10 V, 1 m
STP63 4884
Rotary actuators for ball valves AC 24 ,
DC 0…10 V
GDB161.9E 4657
Type of unit Product no. Datasheet
*)
Rotary actuators for ball valves KNX S-
Mode
GDB111.9E/KN A6V10725318
*)
The documents can be downloaded from http://siemens.com/bt/download
1)
With PWM control, exact parallel run of 2 or more thermal actuators is not
possible . If several fan coil units are controlled by the same room thermostat,
motorized actuators with On/Off or 3-position control are preferred.
For more information about parallel operation and the max. number of actuators
that can be used, refer to the data sheets of the selected actuator type and the
following list:
Max. number of actuators in parallel on RDG200KN (AC 230 V):
● 6 SS..31.. actuators (3-position)
● 4 ST..23.. if used with On/Off control signal
● 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
● Parallel operation of SAS31 not available
Max. number of actuators in parallel on RDG200KN (AC 24 V):
● 6 SS..81.. actuators (3-position)
● 4 ST..73.. if used with On/Off control signal
● 2 SFA71.. On/Off actuators
● Parallel operation of SAS81 not available
Max. number of actuators in parallel on RDG260KN (AC 24 V):
● 10 SS..61.. actuators (DC)
● 10 ST..23/63/73.. actuators (DC or On/Off)
● 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
● 10 SAS61.. actuators (DC)
● 10 GDB161.9E
DC 0…10 V actuators
KNX actuators
Note: