User Manual

Connection
Application examples
6
A6V11545892_en--_a 129 | 146
6.3 Application examples
The examples are described with RDG260KN, but they are also valid for
RDG200KN. Control output (P201, P204) and terminals for the valves (Y1, Y2)
need to be adapted accordingly.
6.3.1 Humidity control
In the following examples, P461 is configured based on the connected type of
equipment. See details in Humidity [ 50].
2-pipe fan coil application for dehumidification, with temperature setpoint shifting
and dehumidifier contact, DC 0...10 V fan and DC valve:
Commissioning Outputs used
Fan P351 = 3
(or DIP6 = OFF)
Control strategy P450 = 1
Setpoint high P024 = 50 %
(factory setting)
Temp. shift P461 = 3 K
(factory setting)
Valve P201 = 5
Relay function P402 = 7
(dehumidifier)
M1 DC 0...10 V fan
V1 DC valve
L3
*)
Dehumidifier
*)
Release contact
See Technical data [ 137] for min. and max. ratings
RDG260KN
Note:
Example 1: Dehumidifier,
DC 0...10 V fan and valve