To start this application, select Applications ➙ Plant operation ➙ Standard
diagram.
The ACS tool provides standard plant diagrams for RDG2..KN room thermostats,
depending on the following configurations:
Plant type Application
Configuration
Application
Configuration
2-pipe 2-pipe fan coil unit
–
Control sequence: No impact
(
P001
= any)
–
Fan operation: Enabled (
P350
<> 0)
Single stage with electric heater
–
Control sequence: No impact (
P001
= any)
–
Fan operation: Disabled (
P350
= 0)
Chilled/heated ceiling
– Control sequence: Changeover
– Fan operation: Disabled (P350 = 0)
Chilled ceiling
– Control sequence: Cooling only
(
P001
= 1)
– Fan operation: Disabled (P350 = 0)