User Manual

Functions
Control parameters
4
A6V11545892_en--_a 107 | 146
4.15.4 Parameters of the Service level
Parameter
Name Factory
setting
Range
RDG200KN
RDG260KN
Dependencies
Service level
P001 Control sequence
1)
2-pipe:
1 = Cooling
only
4-pipe:
4 = Heating
and cooling
0 = Heating only
1 = Cooling only
2 = H/C changeover auto
3 = H/C changeover manual
4 = Heating and cooling
P002
P002 Operation via room operating mode
selector
1)
1 1 = Auto (Comfort) – Protection
2 = Auto - Comfort - Economy - Protection
3 = Auto (Comfort) - Protection Hospitality
P001
P003 Operation via fan operating selector
2)
0 0 = Auto - Manual
1 = Manual
2 = Auto - Manual - Protection
3 = Auto – Protection
P350
P004 Unit 0 0 = °C (parameter in °C)
1 = °F (parameter in °F)
P006 Measured value correction 0 K –5…5 K
P007 Humidity value correction 0 -10…0…10 %
P008 Standard display 0 0 = Room temperature
1 = Setpoint
P009 Additional display information 0 0 = --- (No display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12 h) (via bus)
4 = Time of day (24 h) (via bus)
5 = Humidity
P010 Setpoint concept 1 1 = Comfort concept
2 = Energy saving concept
P104
P011 Comfort basic setpoint 21 °C (70 °F) 5…40 °C (41…104 °F)
P013 Comfort setpoint minimum 5 °C (41 °F) (P010 = 1): 5 °C (41 °F)...P016-1 K
(P010 = 2): 5 °C (41 °F)...P014-1 K
P010
P014 Comfort setpoint maximum heating 21 °C (70 °F) P013+1 K…P015-1 K P010
P015 Comfort setpoint minimum cooling 25 °C (77 °F) P014+1 K…P016 -1 K P010
P016 Comfort setpoint maximum 35 °C (95 °F) (P010 = 1): P013 +1 K...40 °C (104 °F)
(P010 = 2): P015 +1 K...40 °C (104 °F)
P010
P019 Economy heating setpoint 15 °C (59 °F) OFF (0), 5 °C…P020 (41 °F…P020)
P020 = 40 °C max. (P020 = 104 °F max.)
P020 Economy cooling setpoint 30 °C (86 °F) OFF (0), P019…40 °C (P019…104 °F)
P019 = 5 °C min. (P019 = 41 °F min.)
P024 Humidity setpoint high 50 OFF (0), P026 or 20…90 % P450
P026 Humidity setpoint low OFF OFF (0), 20…90 % or P024 P450
P027
3)
Electric heater when cooling ON ON: Enabled
OFF: Disabled
Appl