User Manual

Functions
Control parameters
4
106 | 146 A6V11545892_en--_a
Antenna area
Unpowered thermostat from individual
package
DIP switches setting has higher priority meaning that:
If all DIP switches are set to OFF (default), the PCT Go App can change the
application (e.g 2-pipe)
If an application is set via DIP switches, the PCT Go APP cannot change it.
Change setting while the device is powered and running:
Application settings requires a reboot of the device.
Setting such as setpoint and HMI tuning takes effect few seconds later.
Change setting while the device is unpowered:
Current settings of the thermostat can be read and write any time while
unpowered
The thermostat needs to be powered on in order to store the new settings and
ensure that they are correct.
Each time the application is changed, the thermostat reloads the factory setting
for all control parameters, except KNX device and zone addresses.
The thermostat setting access can be protected by password (P502) The PCT
Go APP requires the password to read and write protected settings.
If the password is mistyped 5 times, the thermostat is locked, and a password
cannot be entered for 5 minutes.
The commissioning via Siemens smartphone application PCT Go for Android
can be disabled via parameters to avoid any unexpected changes of
thermostat (P500).
Notes
Security