RDG200KN & RDG260KN Room Thermostats with KNX Communications Basic Documentation A6V11545892_en--_a 2020-09-07 Smart Infrastructure
Table of Contents 1 1.1 1.2 1.3 1.4 About this document ............................................................................. 5 Revision history ...........................................................................................5 Reference documents..................................................................................5 Before you start ...........................................................................................6 1.3.1 Trademarks ..................................
4.7 4.6.8 NFC communication....................................................................53 Control sequences .....................................................................................54 4.7.1 Sequence overview (setting via P001).........................................54 4.7.2 Application mode ........................................................................55 4.7.3 2-pipe fan coil unit .......................................................................57 4.7.
6 6.1 6.2 6.3 Connection ....................................................................................... 125 Connection terminals ............................................................................... 125 Connection diagrams ............................................................................... 126 Application examples ............................................................................... 129 6.3.1 Humidity control .........................................................
About this document 1 Revision history 1 About this document 1.1 Revision history Edition Date Changes Section 1 September 2020 First version. All 1.2 Reference documents Subject Ref. Document title Document number Room thermostats with KNX communications, RDG2..
1 About this document Before you start 1.3 Before you start 1.3.1 Trademarks The table below lists the third-party trademarks used in this document and their legal owners. The use of trademarks is subject to international and domestic provisions of the law. Trademarks Legal owner SyncoTM AndroidTM Google Inc. All product names listed in the table are registered (®) or not registered (™) trademarks of the owner listed in the table. We forgo the labeling (e.g.
About this document 1 Target audience, prerequisites 1.4 Target audience, prerequisites This document assumes that users of the RDG2..KN room thermostats are familiar with the ETS tool, Synco ACS tool or both and can use them. It is also assumed that these users are aware of the specific conditions associated with KNX. In most countries, specific KNX know-how is conveyed through training centers certified by the KNX Association (see www.knx.org/).
2 Overview Types 2 Overview 2.1 Types For fan coil units, universal applications and compressors in DX-type equipment applications Operating voltage Product no. Stock no.
Overview Functions General functions ● ● ● ● ● ● ● ● ● ● ● ● Setpoints and display ● ● ● ● Setting ● ● ● Fan ● ● ● ● ● Special functions ● ● ● ● A6V11545892_en--_a 2 Room temperature control via built-in temperature sensor or external room temperature/return air temperature sensor Room relative humidity control via built-in humidity sensor (humidity function can be disabled.) Min./max.
2 Overview Accessories ● ● Inputs/outputs ● ● KNX communication features ● ● ● ● ● ● ● ● ● Control of 6-port ball valve via KNX S-Mode objects (RDG200KN and RDG260KN) Flow limitation function for PICV in heating mode (RDG260KN) 3 multifunctional inputs selectable for: – Window contact switches operating mode to Protection – Presence detector switches operating mode to Comfort – Sensor for automatic heating/cooling changeover – Switch for manual heating/cooling changeover – External room temperature o
Overview 2 Equipment combinations 2.4 Equipment combinations Type of unit Cable temperature or changeover sensor, cable length 2.5 m NTC (3 kΩ at 25 °C) 1840 Cable temperature sensor PVC 2 m, LG-Ni1000 QPA22 1831 Room temperature sensor NTC (3 kΩ at 25 °C) QAA32 1747 Room temperature sensor LGNi1000 QAA24 1721 Front modules with passive temperature measurement LGNi1000 AQR2531ANW 1408 Strap-on temperature sensor LGNi1000 QAD22 1801 Condensation monitor QXA21.. A6V10741072 AQR2570N..
2 Overview Equipment combinations On/Off and PWM actuators 1) 3-positon actuators AC 230 V 3-positon actuators AC 24 V 12 | 146 Type of unit Product no. Thermal actuator (for radiator valves) AC 230 V, NO STA23.. 1) 4884 Thermal actuator (for radiator valves) AC 24 V, NO STA73.. 1) 4884 Thermal actuator AC 230 V (for small valves 2.5 mm), NC STP23.. 1) 4884 Thermal actuator AC 24 V (for small valves 2.5 mm), NC STP73.. 1) 4884 Type of unit Datasheet *) Product no.
Overview 2 Equipment combinations DC 0…10 V actuators KNX actuators Type of unit Product no. Datasheet *) Electric actuator, DC 0…10 V (for radiator valves) SSA61.. 4893 Electric actuator, DC 0…10 V (for 2and 3-port valves/V..P45) SSC61.. 4895 Electric actuator, DC 0…10 V (for small valves 2.5 mm) SSP61.. 4864 Electric actuator, DC 0…10 V (for small valves 5.5 mm) SSB61.. 4891 Electromotive actuator, DC 0…10 V (for valves 5.5 mm) SAS61..
2 Overview Integration via KNX bus 2.5 Integration via KNX bus The RDG2..
Overview 2 Integration via KNX bus Legend Desigo and third-party systems A6V11545892_en--_a Synco 700 Building automation and control system (BACS) Gateway Connection of meters via Modbus OZW Web server, connection of Synco, RDG/RDF & GAMMA RMB Central control, RDG/RDF integration RDG/RDF Thermostats for Room climate control Gamma Instabus For lighting control and other room electrical applications The RDG2..
3 Notes Mounting and installation 3 Notes 3.1 Mounting and installation Mounting ● ● ● ● ● ● ● ● Wiring ● The devices are suitable for wall mounting. Recommended height: 1.5 m above the floor. Do not mount the devices in recesses, shelves, behind curtains or doors, or above or near heat sources. Avoid direct solar radiation and drafts. Avoid unheated (uncooled) building area such as outside walls. Seal the conduit box or the installation tube if any, as air currents can affect sensor readings.
Notes 3 Commissioning ● Disconnect thermostat from power supply before removing from the mounting plate. ● If a KNX bus power supply is connected to the line with communicating thermostats and Synco controller, the internal KNX power supply of the Synco controllers must be switched off. 3.2 Commissioning Applications and settings The room thermostats are delivered with a fixed set of applications and related parameters.
3 Notes Commissioning ACS and ETS require an interface: ● KNX interface (e.g. Siemens N148…) ● OCI702 USB-KNX interface Control sequence Set the control sequence via parameter P001 depending on the application.
Notes 3 Operation 3.3 Operation The room thermostat consists of two parts: ● Plastic housing with electronics, operating elements and room temperature sensor ● Mounting plate with the screw terminals The housing engages in the mounting plate and is secured with 2 screws.
3 Notes Operation User action Effect, description Press left button while "Operating mode" via bus is Economy Activate "Extend Comfort mode" (for details, see Different ways to influence the operating mode [➙ 27]). Keep left button pressed and turn rotary Activate timer "Extend knob clockwise/counter-clockwise presence"/"Extend absence" and set the time (for details, see Different ways to influence the operating mode [➙ 27]. Press right button >3 seconds Activate/deactivate button lock.
Notes 3 Remote operation # Symbol Description # Symbol Description 10 Parameter 11 Value with thermometer: Digits for room temperature display 12 Digits for setpoint display 13 Protection mode 14 Economy mode 15 Comfort mode 16 Cooling mode 17 Heating mode, electric heater active 18 Heating mode 19 Manual changeover, heating/cooling mode 20 Auto mode 21 Temporary timer 22 Fault 23 Button lock 24 Condensation in room 25 (dewpoint sensor active) or humidity control active
4 Functions Temperature control 4 Functions 4.1 Temperature control General note: Parameters Setting of the control parameters (P001 and so on, mentioned throughout the document), see Control parameters [➙ 104].
Functions 4 Operating modes When an application program is downloaded to the Synco devices via ETS, the correct group addresses must also be downloaded in order to display the time of day on the thermostat (see Synco Knowledge Base - KB771). Note 4.2 Operating modes Room operating mode: State The thermostat operating mode can be influenced in different ways (see Different ways to influence the operating mode [➙ 24]). Specific heating and cooling setpoints are assigned to each operating mode.
4 Functions Operating modes For details regarding the window contact and presence detector, see Different ways to influence the operating mode [➙ 24]. Note *) 4.2.1 Different ways to influence the operating mode Source for change of operating mode ACS Different interventions can influence the operating mode. The source of the actual room operating mode state can be monitored using the "Cause" diagnostic data point in the ACS tool or web server OZW772.
Functions 4 Operating modes Priority Description ④ Presence detector Remark ● Standard presence mode: If room is occupied, the operating mode changes to Comfort. This overrides the operating mode on the thermostat. Unoccupied room will set the thermostat back to the previous operating mode. ● Hotel presence mode: If room is unoccupied, the operating mode changes to Economy. This overrides the operating mode on the thermostat. The buttons are locked and icon displays.
4 Functions Operating modes Behavior when bus sends new operating mode Each time the time schedule sends a new operating mode (switching event), the operating mode of the thermostat is set back to Auto mode. This ensures that the room temperature is maintained according to the time schedule. Precomfort via bus If the time schedule sends Precomfort mode, then this mode is transformed either to Economy (factory setting) or Comfort (selectable via P910).
Functions 4 Operating modes The operating mode can be changed to Comfort or Economy mode based on the room occupancy (room occupied or unoccupied, via presence detector or keycard). For details, see Presence detector [➙ 43] Presence detector Temporary timer to extend Comfort mode can be temporarily extended (for example, working after business hours or on weekends) when the thermostat is in Economy mode. Comfort mode 1.
4 Note Functions Operating modes User profile for operating mode (selected via P002) Operating mode when activating function P002 = 3: Comfort Extension Comfort Protection hospitality Comfort Absence Protection hospitality Comfort Operating Operating mode during mode at the function end of function Extension/absence function is not available in Protection mode.
Functions Operating modes 4 Example 1 Window contact In Room 1, the window is opened briefly, once in the morning and once in the late afternoon (1). The opening in the morning and afternoon has a direct impact on the actual room operating mode. During lunch break (2), the time schedule changes to Precomfort. The mode remains in Comfort as set by parameter "Transformation Precomfort" (P910 = 1).
4 Functions Operating modes Example 3 30 | 146 Application for "Window Contact", "Presence Detector" and “Central time schedule” In Room 3, the time schedule set available between 13:00 and 17:00.
Functions Room temperature setpoints 4 4.3 Room temperature setpoints 4.3.1 Description Comfort mode The factory setting for the Comfort basic setpoint is 21 °C and can be changed in the thermostat’s EEPROM via P011, bus with communication object "Comfort basic setpoint" or Siemens smartphone application PCT Go for Android. The last option selected is always used. The Comfort setpoint can be adjusted via the rotary knob, or bus from a remote device like a touch panel, operating unit, and so on.
4 Functions Room temperature setpoints Setpoint limitation For comfort or energy saving purposes, the setpoint setting range can be limited by selecting the most appropriated setpoint concept: ● Setpoint Comfort concept (P010 = 1) for the maximum comfort of the user ● Setpoint energy saving concept (P010 = 2) for energy saving purposes Setpoint comfort concept (P010 = 1) ● ● ● Example Setpoint energy saving concept (P010 = 2) The setpoint limit can be set via P013 (Comfort setpoint minimum) and P016
Functions 4 Room temperature setpoints CAUTION If a setpoint (Economy or Protection) is set to OFF, the thermostat does not control the room temperature in the corresponding mode (heating or cooling). In other words, there is no protective heating or cooling function and thus risk of frost in heating mode or risk of overtemperature in cooling mode! The Economy setpoints (P019, P020) are accessible at the Service level; the Protection setpoints (P100, P101) are accessible at the Expert level. 4.3.
4 Functions Room temperature setpoints Only required for heating and cooling applications (see Setpoints and sequences [➙ 73]) 2) LTE-Mode: Shift is added to the local shift 3) S-Mode: The last option selected is always used, either S-Mode input or local operation 4) To display the S-Mode objects of the Economy heating and cooling setpoint (P019/P020), set the control parameter “Room temperature: Economy setpoints” to as group object in ETS tool 5) Other functions: ● If current humidity setpoint is not su
Functions 4 Room temperature setpoints 2-pipe with P010 = 1 or 4-pipe with P010 = 1 and P001 = 3 Both the Comfort setpoint w and current setpoint w2 have the same values. 4-pipe with P010 = 1 The Comfort setpoint w (value selectable via for example, rotary knob) is in the middle of the dead zone (P055). The current setpoints w2.. (used by the thermostat for temperature control) are at the boundaries of the dead zone.
4 Functions Applications overview 4.4 Applications overview The RDG2..KN room thermostats support the following applications, which can be configured using the DIP switches at the rear of the unit or commissioning tool. Remote configuration Set DIP switches 1…5 to OFF (remote configuration, factory setting) to select an application via commissioning tool.
Functions Applications overview 4 4.4.
Functions 4 Applications overview 4.4.
Functions Applications overview 4 4.4.
4 Functions Power supply selection for RDG200KN 4.5 Power supply selection for RDG200KN The RDG200KN can be powered either in AC 230 V or AC 24 V. The desired power supply needs to be selected via the power switch located in the rear of the device. The default setting is AC 230 V.
Functions 4 Additional functions 4.
4 Functions Additional functions 4.6.1 Sensors and changeover functions Heating/cooling changeover via bus (KNX) The heating/cooling changeover information can be received via bus. This is only possible if the control sequence is set to automatic heating/cooling changeover (P001 = 2) and no local input (X1, X2, U1) is assigned with this function. In the absence of the required information (for example, due to problems with data communication, power failure, and so on.
Functions 4 Additional functions P151 (X1), P154 (X2) or P156 (U1) = 0 (default, Normally open) P151 (X1), P154 (X2) or P156 (U1) = 1 (Normally close) Contact open Contact open ⇨ heating mode Contact closed ⇨ cooling mode Manual heating/cooling changeover (P001) ● ● External/return air temperature sensor (P150, P153, P155) ⇨ cooling mode Contact closed ⇨ heating mode Manual heating/cooling changeover means selection via changeover button on the thermostat by repeatedly pushing the button until
4 Functions Additional functions Time schedule via Bus Presence detector behavior Comfort mode Whenever the hotel guests leave their rooms (room is unoccupied), the operating mode goes to Economy. The buttons are locked and icon Economy mode ● displays. Whenever the hotel guests leave their rooms (room is unoccupied), the operating mode goes to Economy. The buttons are locked and icon ● displays. Whenever the room is occupied, the operating mode goes to previous operating mode from Economy.
Functions 4 Additional functions The swap function optimizes the use of heating/cooling energy in mixed systems. For example, when the fan coil units are combined with radiant heating/cooling panels, it is more appropriate to start heating with the panels (1st stage heating, YHC1) and start cooling using the fan coil unit (1st stage cooling, YHC2). Enable the swap function by setting P254 (YHC2 output signal, 1st stage in cooling) to ON, depending on the requested control signal.
4 Functions Additional functions these functions are required, the total maximum current on the relay outputs (Q1+Q2+Q3) must not exceed 2 A.
Functions 4 Additional functions To reduce wear and tear on the HVAC equipment, the minimum output On/Off time of the Qx relay output can be adjusted (1…20 minutes) via P212 and P213. The factory setting is 1 minute. When the operating mode is changed from Comfort to Economy or Protection, the relay contact remains energized until the end of the minimum on time set via P212. Note 4.6.
4 Functions Additional functions Note ● ● This function is only active in Comfort mode with: – Valve output type is 3-position (RDG200KN) or DC 0...10 V (RDG260KN) – Electric heater is PWM / 3-position (RDG200KN) or DC 0...10 V (RDG260KN) This function can not be used for radiators.
Functions 4 Additional functions Note When condensation is detected with ● Control only with 6-port control ball valve: o When P201 = 6 or 8, the valve will be close (5 V). o When P201 = 7 or 9, the valve will be close (6 V). ● Control with combi-valve (PICV): The PICV will be closed and the 6-port ball valve will not. The condensation symbol displays during temporary override and the fault "Condensation in room" is sent via bus.
4 Functions Additional functions Within the preset energyefficient range Exceed the preset energyefficient range End users can press the red leaf and return to the energyefficient range Return to the preset energyefficient range Maximum tolerance of room temperature setpoint shift value is defined by P111 (default is 2 K). 4.6.
Functions Additional functions Setpoint high Setpoint low 4 The low humidity setpoint (%) is selectable via P026 (setpoint humidity low) and can be adjusted via parameters in Service level or via bus. Setting P026 to OFF (default setting) disables low humidity control. The setting range is limited by P024. S-Mode objects for the humidity setpoint are available when the parameter "Humidity setpoints" is set to as group object in ETS.
4 Functions Additional functions To enable the relay function, set P400 (output Q1), P401 (output Q2) or P402 (output Q3) to 8. The humidification S-Mode object sends ON to the bus as soon as the output is energized. Humidification When the humidity falls below the low setpoint or exceeds the high setpoint, the symbol is displayed and the S-Mode object HumDehumMode sends the HumDehumMode corresponding state on the bus. Max.
Functions Additional functions 4 Note This setting is typically used for cooling applications with fan coil units or split units. When the thermostat is in cooling mode or in the dead zone, the temperature setpoint cooling is shifted only when P461 is less than 0 K. The temperature setpoint heating, if available, remains unchanged. The thermostat guarantees a minimum dead zone between both setpoints. P461 = 0 K When P461 is set to 0 K, the temperature setpoint heating, cooling or both are not shifted.
4 Functions Control sequences For the info about commissioning via Siemens smartphone application PCT Go for Android, see Commissioning. 4.7 Control sequences 4.7.1 Sequence overview (setting via P001) The main control sequence (that is, the water coil sequence of the fan coil unit) can be set via P001. The following sequences can be activated in the thermostats (with or without auxiliary heating).
Functions 4 Control sequences 4.7.2 Application mode Application mode The behavior of the thermostat can be influenced by a building automation and control system (BACS) via bus using the command "Application mode". Cooling, heating or both activities can be enabled or disabled using this signal. Application mode is supported in LTE-Mode and S-Mode. The RDG2..
4 Functions Control sequences Application mode (via bus) State changeover/continuous heating or cooling Control sequence state (ACS diagnostic value) Auto (0) Heating Heating Cooling Cooling Heating Heating Cooling Heating Heating Cooling Cooling Cooling Heating Heating Cooling Cooling Heat (1), (2), (8) Cool (3), (5) Night purge (4), Fan only (9) Heating and cooling With a 4-pipe, 2-pipe with electric heater, and 2-pipe with radiator application, the control sequence state is based o
Functions 4 Control sequences 4.7.3 2-pipe fan coil unit On 2-pipe applications, the thermostat controls a valve in heating/cooling mode with changeover (automatically or manually), heating only, or cooling only (factory setting, P001 = 1). On/Off control Control sequence On/Off control output The diagrams below show the control sequence for On/Off control.
4 Functions Control sequences 4.7.4 2-pipe fan coil unit with electric heater Heating or cooling with auxiliary heater On 2-pipe applications with electric heater, the thermostat controls a valve in heating/cooling mode with changeover, heating only, or cooling only plus an auxiliary electric heater. Cooling only is factory-set (P001 = 1) with enabled electric heater (P027).
Functions 4 Control sequences In this case that an electric heater is connected directly to outputs Q2 (RDG260KN), the current causes the relay contact to heat up. This falsifies the reading of the internal temperature sensor. The thermostat compensates the temperature if the rated power of the electric heating is entered at P217. Factory setting P217: 0.0 kW, setting range: 0.0…1.2 kW. On/Off control Control sequence On/Off output The diagrams below show the control sequence for On/Off control.
4 Functions Control sequences 4.7.5 2-pipe fan coil unit with radiator or floor heating Heating or cooling with radiator or floor heating On 2-pipe applications with radiator, the thermostat controls a valve in heating/cooling mode with changeover, heating only, or cooling only plus a radiator valve. Cooling only is factory-set (P001 = 1). Radiator, active in cooling mode In cooling mode, the valve receives an OPEN command if the acquired temperature is above the setpoint.
Functions 4 Control sequences Heating mode Cooling mode T[°C] Room temperature XpH Proportional band "Heating" (P050) w Room temperature setpoint XpC | Proportional band "Cooling" (P052) Control command "Valve" or "Compressor" XpR Proportional band "Radiator" (P054) Control command "Radiator" Xdz Dead zone (P055) wD Setpoint differential (P056) YHC YR Note The diagrams only show the PI thermostat’s proportional part.
4 Functions Control sequences 4.7.6 2-pipe/2-stage heating or cooling 2-stage heating or cooling On 2-stage applications, the thermostat controls 2 valves or 2-stage compressors in heating or cooling mode or changeover (automatically or manually). "Cooling only" is factory-set (P001 = 1). Heating mode In heating mode, the 1st stage is activated if the acquired temperature is below the setpoint.
Functions 4 Control sequences T[°C] w YHC1 YHC2 Modulating control: 3-position, PWM or DC 0…10 V Room temperature Room temperature setpoint Control command "Stage 1" Control command "Stage 2" SDH SDC wD Switching differential "Heating" (P051) Switching differential "Cooling" (P053) Setpoint differential (P056) The diagrams below show the control sequence for modulating PI control.
4 Functions Control sequences 4.7.7 4-pipe fan coil unit Heating and cooling On 4-pipe applications, the thermostat controls 2 valves in heating and cooling mode, heating/cooling mode by manual selection, or heating and cooling mode with changeover. Heating and cooling mode (P001 = 4) is factory-set. 4-pipe application with manual changeover The heating or cooling output can be released via operating mode button if P001 is set to Manual (P001 = 3).
Functions 4 Control sequences Heating mode with manual selection (P001 = 3) or for energy saving (P010 = 2 & P014) in heating sequence Note A6V11545892_en--_a Cooling mode with manual selection (P001 = 3) or for energy saving (P010 = 2 & P015) in cooling sequence The diagrams only show the PI thermostat’s proportional part. For setting sequence and control outputs, see Applications overview [➙ 36], Sequence overview (setting via P001) [➙ 54] and Control outputs [➙ 75].
4 Functions Control sequences 4.7.7.1 4-pipe application with PICV and 6-port control ball valve as changeover (RDG260KN) On a 4-pipe fan coil application with DC 0...10 V fan control, the RDG260KN controls a combi valve (PICV) in combination with a 6-port ball valve as changeover. Note: Set DIP# 1 & 4 to ON (4-pipe with 6-port ball valve as changeover and PICV). Principle This application is used on 4-pipe systems with one heat exchanger and differential pressure controller (using a PICV).
Functions 4 Control sequences 4.7.8 4-pipe fan coil unit with electric heater Heating and cooling with auxiliary heater On 4-pipe applications with electric heater, the thermostat controls 2 valves in heating and cooling mode by manual selection, heating only, or cooling only plus an auxiliary electric heater. Heating and cooling is factory-set (P001 = 4).
4 Functions Control sequences Modulating control: 3-position or PWM The diagrams below show the control sequence for modulating PI control.
Functions 4 Control sequences 4.7.9 Chilled/heated ceiling and radiator applications For chilled/heated ceiling and radiator applications ● Set the corresponding basic application see Applications overview [➙ 36].
4 Functions Control sequences Kv YC YH W Y Hydraulic and control diagram of the 6-port control ball valve loop W YH YC Kv Room temperature setpoint Control command "Valve" (heating) Control command "Valve" (cooling) Flow through the valve Default Integral action time TN is fix to 45 minutes.
Functions 4 Control sequences 4.7.9.2 Chilled/heated ceiling with Pressure Independent Combi Valve and a 6-port ball valve as changeover (RDG260KN) The RDG260KN is able to control a Pressure Independent Combi Valve (PICV) for a chilled and heated ceiling application in combination with a 6-port ball valve as changeover.
4 Functions Control sequences When control sequences change, the thermostat closes the combi valve and releases the corresponding relay to operate the ball valve. A delay of 120 seconds is needed before the combi valves can be operated by the thermostat. When the relay to ensure the ball valve is on the right H/C position, the control signal for the combi valve is released.
Functions 4 Control sequences 4.7.11 Applications with external AQR sensor or QMX room operator unit The equipment combination is for use in commercial buildings, offices, schools, museums, shops, and so on. Advantages of equipment combination AQR/QMX sensor LTE-Mode S-Mode With sensor AQR25.. or QMX3..0 4.7.12 2-pipe applications A6V11545892_en--_a a) Sensor can be installed in the optimal place for temperature and humidity measurement.
Functions 4 Control sequences Application Comfort mode Heating Economy/Protection mode Cooling Heating Cooling 2-pipe 2-pipe with electric heater 2-pipe with radiator 2-pipe/ 2-stage heating or cooling If P027 = ON W = setpoint in Comfort mode WHeatEco/Prot = setpoint heating in Economy or Protection mode WCoolEco/Prot = setpoint cooling in Economy or Protection mode YR = radiator sequence YE = electric heater sequence 1) 4-pipe applications 74 | 146 On 4-pipe applications, the Comfort setpoi
Functions 4 Control outputs Application Comfort mode Heating and cooling P010 = 1 Economy/Protection mode Heating only or heating and cooling P010 = 1 1) Cooling only and cooling P010 = 2 1) or heating Heating and/or cooling 4-pipe 4-pipe with electric heater Manual changeover, P001 = 3 W = setpoint in Comfort mode WHeatEco/Prot = heating setpoint for Economy or Protection mode WCoolEco/Prot = cooling setpoint for Economy or Protection mode YE = electric heater sequence 1) 4.
4 Functions Control outputs 1. the acquired room temperature is below the setpoint (for heating mode) or above the setpoint (for cooling mode), 2. the control outputs have been inactive for more than the "Minimum output off time" (factory setting 1 minute, adjustable via P213). The valve receives the OFF command when… 1. the acquired room temperature is above the setpoint (for heating mode) or below the setpoint (for cooling mode), 2.
Functions 4 Control outputs PWM control (RDG200KN only) The demand calculated from the current room temperature and setpoint is provided via Y1, Y2 and Y3 to the valve actuator as a PWM (pulse width modulation) signal for thermal actuators. The control output is activated for a period proportional to the heating/cooling demand and then switched off for the rest of the PWM interval. The PWM algorithm cycle time is 1200 seconds (factory setting). It can be adjusted via P206 (Y1), P207 (Y2) or P208 (Y3).
4 Functions Control outputs DC 0...10 V for electric heaters ● ● ● Note The demand calculated by PI control from the current room temperature and setpoint is provided via Y20 as a continuous DC 0...10 V signal The signal converter (SEM61.4) converts the DC 0...10 V signal to AC 24 V PDM pulses for the current valve The current valve (SEA45.1) supplies the electric heater with pulsed current The electric heater can be controlled via the On/Off control output (Q2) by setting P203 or P204 to 4.
Functions 4 Control outputs 4.8.2 Control output configuration (setting via DIP switches 7/8 or tool, and P201/P203/P204) Overview Application Fan DC 0...10 V 3-speed/ 1-speed 2-pipe Product no. Control outputs Mod. DC 0…10 V On/Off On/Off Mod. PWM Mod. 3-pos.
Functions 4 Control outputs DIP NO.: 7…8 ➨ ON = , OFF = Y1/Y3 = 2-position (PWM) 2-position (PWM) 3-position 3-position Y2/Y4 = 2-position (PWM) 3-position 2-position (PWM) 3-position Notes ● If 2-position (PWM) is selected via DIP switches, the control output is On/Off (factory setting). To select PWM (pulse width modulation), set P201, P203 and/or P204 to 3. ● 4-pipe with electric heater: As the electric heater requires 1 of 4 outputs, only the cooling valve actuator can be 3-position.
Functions Fan control 4 4.9 Fan control Overview fan outputs On RDG200KN and RDG260KN, the available fan output signals are one On/Off 1speed/3-speed fan or one modulating fan DC 0...10 V and control type can be selected via P351. The fan control signal (DC 0…10 V or 3-speed) is selected via DIP switch 6, local HMI (P351) or tool (ACS, ETS or Siemens smartphone application PCT Go for Android). The fan operates in automatic mode or at the selected speed with manual mode.
4 Functions Fan control Fan control with modulating heating/cooling control (PWM, 3-pos or DC 0...10 V) For 3-speed fan control: The individual switching points for ON of each fan stage can be adjusted via control P353…P355. The fan speed switch off point is 20% below the switch on point. The diagrams below show fan speed control for modulating PI control. For DC 0…10 V fan control: When DC 0...
Functions Fan control Fan control with On/Off heating/cooling control 4 On applications with On/Off control: 1. The switching point for low fan speed is synchronized to the heating/cooling output. P353 (switching point fan speed low) is not relevant. 2. The maximum switching range of the fan (XpHFan /XpCFan) is defined by the switching differential (SDH/SDC) via a look-up table. Heating/cooling 1- or 3-speed fan DC 0...
4 Functions Fan control Fan speed III = max. fan speed selectable via P359 (heating), P360 (cooling) Note: Manual fan settings do not influence control signals "Heating" and "Cooling". Note When heating with the electric heater only, manual fan speed I is unavailable to guarantee the necessary minimum air flow for the electric heater and to avoid overheating of the system. 2 sequences heating/cooling For heating or cooling with 2 sequences (e.g.
Functions 4 Fan control Notes ● ● The output for the 1st stage (YHC1) in heating mode is also the 1st stage in cooling mode This function is available for DC/3-speed/1-speed fans Example 2 We recommend enabling the swap function on applications with fan coil system and floor heating/cooling systems. In this application, the fan runs during cooling demand (fan coil unit and floor cooling) and only in the 2nd heating stage (with the fan coil unit).
4 Functions Fan control Combination 1st stage 2nd stage signal signal Fan type Fan synchro Fan behavior 6 On/off DC DC 2nd sequence XpH/XpC, P/PI control 7 DC On/off DC 1st sequence XpH/XpC, P/PI control 8 DC On/off DC 2nd sequence 9 DC DC 3-speed 1st sequence XpH/XpC, P/PI control 10 DC DC 3-speed 2nd sequence XpHFan /XpCFan, P-control XpH/XpC, P/PI control Fan operation as per heating/cooling mode, or disabled Fan operation can be limited to be active with cooling only or he
Functions 4 Fan control ● Auto fan runs in the dead zone at low speed in Cooling mode only (P029 = 2). In heating mode, fan does not run in the dead zone. ● Auto or manual fan does not run in the dead zone (P029 = 3) ● Auto or manual fan runs in the dead zone at low speed in heating and cooling mode (P029 = 4) ● Auto or manual fan runs in the dead zone at low speed in cooling mode only (P029 = 5). In heating mode, fan does not run in the dead zone.
Functions 4 Multifunctional input, digital input Fan operation with combi valve PICV and a 6-port ball valve as changeover Fan control is set to enable by default (P350 = 1), if the thermostat is set with control sequence “H/C ceiling with PICV and 6-port ball valve as changeover”.
Functions Multifunctional input, digital input Type X1/X2/U1 # Function of input Description 4 Dewpoint monitor Digital input for a dewpoint sensor to detect DI condensation. Cooling is stopped if condensation occurs. 5 Enable electric heater Digital input to enable/disable the electric heater via remote control. Enable electric heater is also possible via bus. In this case, do not assign the function to any local input X1, X2, U1. See also Control sequences [➙ 54].
Functions 4 Handling system faults # Function of input Type X1/X2/U1 Description 10 Presence detector Presence detector input switches the operating DI mode to Comfort when the room is occupied and switches back to previous operating mode when the room is unoccupied. Presence detector is also possible via bus. In this case, do not assign the function to any local input X1, X2 or U1. See also Presence detector [➙ 43].
Functions 4 KNX communications Fault “Er1, Er2, Er3, Er4, Er5” on display ● ● If the built-in temperature or humidity sensor fails and no external temperature sensor is connected, fault message Er1 displays on the thermostat. If EEPROM is damaged, fault message Er2 displays on the thermostat. Replace the thermostat if you want the room temperature to be measured.
4 Functions KNX communications Whenever an output and an input with the same "name" are located in the same zone, a connection is established automatically, as shown in the following diagram. Engineering and commissioning ● ● ● 4.12.3 For a detailed description of KNX (topology, bus supply, function and setting of LTE zones, filter tables, etc.
Functions 4 KNX communications Geographical zone (space zone) (Apartment . Room . Subzone) Apartment = ---, 1...126 Room = ---, 1...63 Subzone = fix 1 Zone where an RDG2..KN KNX room thermostat is physically located. Other room-specific devices may also be located in this zone. Information exchanged in this zone is related specifically to the device like operating mode, setpoints, room temperature, and so on. The designations "Apartment", "Room" and "Subzone" are not necessarily literal.
4 Functions KNX communications 4.12.4 Example of heating and cooling demand zone The building is equipped with Synco controls on the generation side and RDF../RDU../RDG.. room thermostats on the room side. Explanation relating to the illustration In the case of a typical application, the individual RDF../RDG.. room thermostats send their heat demand to the primary controller (in the above example to the RMH760). (1) and (2) designate the numbers of the distribution zone. Notes ● ● 4.12.
Functions 4 KNX communications ● ● Reducing the bus load 4.12.6 Receive timeout: 31 minutes Send heartbeat: 15 minutes Object [KNX obj. Nr.] I/O Minutes Default value Room operating mode: Time switch [13] Receive 31 Comfort Application mode [48] Receive 31 Auto Heating/Cooling mode status [46] Receive 31 Heating Individual zones can also be disabled (out of service) via control parameter if they are not being used.
4 Functions Communication objects (S-Mode) Priorities Fault Thermostat Fault information on bus Display Error code Default fault Text text adjustable 1) - No fault --- 0 No fault ✓ 1 Bus power supply 2) BUS 5000 No bus power supply --- 2 Device address error Addr 6001 >1 id device address --- 3 Condensation 4930 Condensati on in the room ✓ 4 External fault input X1 AL1 9001 Fault input 1 ✓ 5 External fault input X2 AL2 9002 Fault input 2 ✓ 6 External fault input
Functions 4 Communication objects (S-Mode) Object No.
Functions 4 Communication objects (S-Mode) 4.13.2 Obj 1 Object name System time Description of communication objects Function Time and date Type/ length 19.001 8 bytes Flags CWU System time for display on the room thermostat. See P009 (3 or 4) 2 Date Date 11.001 3 bytes CWU Obj 9 10 11 12 Object name Function Room operating Trigger mode: Preselection - Auto - Comfort - Economy - Protection Type/ length 1.017 1 bit Flags CW Day, month and year for display on the room thermostat.
Functions 4 Communication objects (S-Mode) Obj 21 Object name Room temp: [P19] Economy heating setpoint Function Type/ length Temperature 9.001 2 bytes Flags CW Communication object adjusts the Economy heating setpoint used by the thermostat (see Setting and adjusting setpoints [➙ 33]). It directly changes the value of the local parameter "Economy heating setpoint" P019. S-Mode object needs to be enabled by setting Room temperature: Economy Setpoint to as group object in ETS.
4 Functions Communication objects (S-Mode) Obj 35 Object name Extended comfort mode status Function ON OFF Type/ length 1.011 1 bit Flags CRT Indicates the status of Comfort mode extension. 36 External room temperature value Temperature 9.001 2 bytes CWU The thermostat receives and works with the room temperature from an external sensor. 37 Built-in room temperature value Temperature 9.
Functions 4 Communication objects (S-Mode) Obj 53 Object name Fan output Function 0…100 % Type/ length 5.001 1 byte Flags CRT Obj 65 Object name Heating, control value status Function Off On Type/ length 1.011 1 bit Flags CRT Indicates the current fan speed as a value 0...100 %.
4 Functions Communication objects (S-Mode) Obj 75 Object name Hum. Control mode Function Inactive Humidification Dehumidification Type/ length 20.115 1 byte Flags CRT Indicates the mode of the humidity control function: 0 = inactive 1 = humidification; relative humidity lower than setpoint low P026 2 = dehumidification; relative humidity higher than setpoint high P024 3…255 = not used 76 Enable electric heater Enable/disable 1.
Functions Communication objects (LTE-Mode) 4 4.14 Communication objects (LTE-Mode) RDG Geographical zone A.R.S Room operating mode: Time switch (Time switch zone) X.1.1/X.Y.1 Application mode Room operating mode: Preselection Geographical zone A.R.S X.Y.1 Room temperature Comfort setpoint Room humidity [%r.h.] Setpoint heating Setpoint cooling Fan speed Setpoint shift heating Setpoint shift cooling Heat distr. zone Heating coil energy demand heating coil Heating/cooling changeover Ref. distr.
4 Functions Control parameters 4.15 Control parameters A number of control parameters can be readjusted to optimize control performance. This can be done on the thermostat via HMI, commissioning/operating tool, or Siemens smartphone application PCT Go for Android. These parameters can also be set during operation without opening the unit. In the event of a power failure, all control parameter settings are retained.
Functions Control parameters 4.15.2 4 Parameters setting/download via tool The control parameters can be adjusted via bus either by parameter download during commissioning or during normal operation with a tool like ACS. With the ACS tool, the parameters can be changed… ● during commissioning via parameter download (all parameters) ● during operations via Popcard (most of the parameters) ACS OZW772 Web server Most parameters can be changed during operations using the OZW772 web server.
4 Functions Control parameters Antenna area Unpowered thermostat from individual package DIP switches setting has higher priority meaning that: ● If all DIP switches are set to OFF (default), the PCT Go App can change the application (e.g 2-pipe) ● If an application is set via DIP switches, the PCT Go APP cannot change it. Change setting while the device is powered and running: ● Application settings requires a reboot of the device.
Functions Control parameters Parameter Service level P001 Control sequence 1) Factory setting Range 2-pipe: 1 = Cooling only 0= 1= 2= 3= 4= 4-pipe: 4 = Heating and cooling Heating only Cooling only H/C changeover auto H/C changeover manual Heating and cooling Dependencies Name RDG260KN Parameters of the Service level RDG200KN 4.15.
Functions 4 RDG260KN Dependencies Name P028 Keypad 0 0= 1= 2= 3= 4= 5= 6= 7= 8= Unlocked Auto lock Manual lock Lock the operating mode Lock the Setpoint shift Lock fan speed Lock operating mode and setpoint shift Lock operating mode and fan speed Lock setpoint shift and fan speed ✓ ✓ ‒ P029 Fan: Dead zone Comfort mode 2) 0 0= 1= 2= 3= 4= 5= Fan disable Low speed (Heat and Cool) Low speed (Cooling only) Fan disable Auto & Manual Low speed (Heat and Cool) Auto & Manual Low speed (Cooling only
Functions Control parameters 4.15.5 4 Parameters of the Expert level with diagnostics and test P050 Heat P-band Xp 2K 0.5…6 K ✓ ✓ ‒ P051 Switching differential heating 1K 0.5…6 K ✓ ✓ ‒ P052 Cool P-band Xp P053 Switching differential cooling P054 Radiator P-band Xp/switching differential 2K 0.5…6 K ✓ ✓ ‒ P055 Dead zone Comfort mode 2K 0.5…5 K ✓ ✓ ‒ P056 Setpoint differential 2K 0.5…5 K ✓ ✓ ‒ P057 1) Integral action time Tn for heating 45 min 0...
Functions 4 Range P155 Input U1 P155: 3 (AI) 2 = H/C changeover (AI/DI) 3 = Window contact [PROT] (DI) 4 = Dewpoint sensor (DI) 5 = Enable electric heater (DI) 6 = Fault input (DI) 7 = Monitor input (Digital)(DI) 8 = Monitor input (Temp) (AI) 9 = Supply air sensor (AI) 10 = Presence detector / card reader (DI) 11 = External temperature limit (AI) 12 = Coil temperature (AI) 13 = Hotel presence detector / card reader (DI) P151 Normal position and sensor input X1 P154 Normal position and sensor input
Functions Control parameters P212 On time minimum 2-pos output 1 min 1…20 min ✓ ✓ ‒ P213 Off time minimum 2-pos output P214 6)) RDG20xKN: Actuator running time Y1 and 150 s Y3 for 3-pos 20…300 s ✓ ‒ P215 6 RDG20xKN: Actuator running time Y2 and Y4 for 3-pos P214: P201 P215: P203 P217 RDG26xKN: Power of electric heater on Q2 0 kW 0.0…1.
Functions 4 Range 0 0= 1= 2= 3= 4= 5= 6= 7= 8= RDG260KN Factory setting Expert level RDG200KN Parameter Name Dependencies Control parameters ✓ ✓ P350, P351 Relay functions P400 9) Output Q1 function P401 9) Output Q2 function P402 Output Q3 function No function Switch OFF in Protection Switch ON in Heat/Cool demand Switch ON in Heat demand Switch ON in Cool demand Heating sequence active Cooling sequence active External dehumidifier control External humidifier control Controller P450
Functions 4 Control parameters Diagnostics and test Parameter Name Range Dependencies Diagnostics and test d01 Application number 0= 1= 2= 3= 4= 5= 6= 7= 8= 9= d02 X1 state "---" = Function not selected 0 = Not activated (for DI) 1 = Activated (DI) 0…49 °C = Current temp.
5 Supported KNX tools ETS 5 Supported KNX tools 5.1 ETS ETS ETS is an engineering tool and is used to fully commission the RDG2..KN room thermostats. ETS can implement the following functions: ● Define and download the physical address ● Define and download the application (plant type, control sequence) ● Set up and download the thermostat's control parameters ● Set up and download group addresses This document does not describe how to operate ETS and how to set up a device.
Supported KNX tools ETS 5 1 Open the project in ETS and select a device. 2 Click Parameters tab, and adjust the control parameters as follows: 3 The Plant type (application), Control Sequence and other control parameters ([Pxx] description) can be downloaded.
5 Supported KNX tools ETS For more details on control parameters, see Control parameters [➙ 104].
Supported KNX tools ACS tool Humidity parameters 5 1 Click Room relative humidity in the left pane and the humidity parameters will display. 2 Adjust the parameters as required. See Control parameters [➙ 104] for more details of control parameters. 3 Select as group object in checkbox of Humidity setpoints, and then the SMode humidity setpoint displays in the Group Objects tab as follows: 4 Select Receive in checkbox of Room relative humidity.
5 Supported KNX tools ACS tool 5.2.1 Parameter setting in ACS In the ACS program, select Plant ➙ Open to open the plant. To start the parameter settings, select Applications ➙ Plant engineering. The application and control parameters can be adjusted and downloaded. Column Line no. contains the parameter number as displayed in the parameter table. See Control parameters [➙ 104].
Supported KNX tools ACS tool 5 Some parameters have a different range in ACS than on the room thermostats. The thermostat does not accept changes that are outside its range. This can be observed online by the fact that a changed value jumps back to the original value. Use the ranges described in the parameter tables in Control parameters [➙ 104]. Note! 5.2.2 Operation and monitoring with ACS In the ACS program, select Plant ➙ Open to open the plant.
5 Supported KNX tools ACS tool Parameter settings in ACS The ACS tool supports parameter settings even during normal operation. To change a control parameter, double click the parameter under Standard popcard to make the settings. Notes ● ● Plant diagram in ACS The ACS tool offers plant diagrams for easy monitoring and operation of the thermostat. 120 | 146 Make sure you have logged on with sufficient access right.
Supported KNX tools ACS tool 5 To start this application, select Applications ➙ Plant operation ➙ Standard diagram. The ACS tool provides standard plant diagrams for RDG2..
5 Supported KNX tools ACS tool Plant type Application Configuration 2-pipe with 2-pipe fan coil unit with electric heater electric – Control sequence: No impact heater (P001 = any) – Fan operation: Enabled (P350 <> 0) 2-pipe with 2-pipe fan coil unit with radiator radiator – Control sequence: No impact (P001 = any) – Fan operation: Enabled (P350 <> 0) 4-pipe Application Configuration Single stage with electric heater – Control sequence: No impact (P001 = any) – Fan operation: Disabled (P350 = 0) Sin
Supported KNX tools ACS tool Plant type Application Configuration Application Configuration 2-pipe/2stage heating or cooling 2-pipe/2-stage fan coil unit 2-pipe/2-stage – Control sequence: No impact (P001 = any) – Control sequence: No impact (P001 = any) – Fan operation: Enabled (P350 <> 0) – Fan operation: Disabled (P350 = 0) 2-pipe/2-stage fan coil unit 2-pipe/2-stage – Control sequence: No impact (P001 = any) – Control sequence: No impact (P001 = any) – Fan operation: 2nd stage (P350 = 4)
5 Supported KNX tools ACS tool 5.2.3 Operation and monitoring with OZW772 HomeControl app for plant control The OZW772 web server enables users to operate a Synco HVAC system from a remote location – via a PC or from a smart phone using the HomeControl app. A start page displays the most important data points. A combination of menu/path navigation enables users to access all data points quickly and straightforwardly. The entire installation can be visualized in the form of plant diagrams.
Connection Connection terminals 6 6 Connection 6.
6 Connection Connection diagrams 6.
Connection Connection diagrams RDG260KN DC 0…10 V fan Application V1 2-pipe YHC V2 YR 4-pipe YH YC DC DC DC On/Off Q2 On/Off DC V1 On/Off On/Off V1 V2 Q1 Q2 YHC Y30 Y50 Q1 Q2 Q3 Y10 Y20 Y30 ✓ ✓ ✓ ✓ V1 ✓ ✓ ✓ ✓ DC DC DC On/Off Y20 V1 V2 Y30 V1 V2 V2 On/Off DC V1 On/Off On/Off V1 V2 Q1 Q2 YH Y10 Y50 Q1 Q2 Q3 Y10 Y20 Y30 ✓ ✓ ✓ ✓ V1 V2 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ Y50 Q1 Q2 Q3 Y10 Y20 ✓ ✓ ✓ ✓ V1 V2 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
6 Connection Connection diagrams RDG260KN Chilled/heated ceiling with 6-port control ball valve 4-pipe with 6-port ball valve as changeover and PICV Application N2 Room thermostat RDG260KN V3 6-port modulating control actuator S1, S2, S3 Switch (keycard, window contact, presence detector etc.) V4 PICV control valve B1, B2, B3 Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.
Connection Application examples 6 6.3 Application examples The examples are described with RDG260KN, but they are also valid for RDG200KN. Control output (P201, P204) and terminals for the valves (Y1, Y2) need to be adapted accordingly. 6.3.1 Humidity control Note: In the following examples, P461 is configured based on the connected type of equipment. See details in Humidity [➙ 50]. Example 1: Dehumidifier, DC 0...
6 Connection Application examples Example 2: Dehumidifier, DC 0...10 V fan + valve, No shifting setpoint 2-pipe fan coil application for dehumidification, with DC 0...10 V fan and DC valve (without temperature setpoint shifting): Commissioning ● Fan ● ● Control strategy Setpoint high ● ● ● Temp. shift Valve Relay function Outputs used P351 = 3 (or DIP6 = OFF) P450 = 1 P024 = 50 % (factory setting) P461 = 0 P201 = 5 P402 = 7 (dehumidifier) ● ● ● M1 DC 0...
Connection Application examples Example 4: Dehumidifier + humidifier/DC 0...10 V fan 6 2-pipe fan coil application for dehumidification, with temperature setpoint shifting, dehumidifier contact, DC 0...10 V fan and DC valve, humidification is controlled by release contact: Commissioning ● Fan ● ● Control strategy Setpoint high ● ● Setpoint low Temp.
6 Connection Application examples 6.3.2 Relay functions Example 1: Switching off the fan coil unit 2-pipe fan coil application, fan coil unit off during Protection mode. Commissioning ● Fan ● ● Valve Relay function Outputs used P351 = 3 (or DIP6 = OFF) P201 = 5 P402 = 1 (Protection mode) ● ● ● ● M1 DC 0...10 V fan V1 DC valve L3*) Fan coil K Relay *) Release contact RDG260KN See Technical data [➙ 137] for min. and max.
Connection Application examples Example 3: Compressor and reversing valve 6 Compressor application, with reversing valve (heating/cooling) and DC 0...10 V fan: Commissioning Outputs used ● ● ● ● ● Application Control output Fan 4-pipe P201 = 4 (On/Off) P351 = 3 (or DIP6 = OFF) Relay function Heating/cooling – ON in demand: P401 = 2 – Energized mode: Heating P401 = 5 – Energized mode: Cooling P401 = 6 M1 DC 0...
6 Connection Application examples 6.3.3 Swap function and/or fan in the 2nd stage Example 1: Fan in the 2nd stage 2-pipe fan coil application for floor heating/cooling (2-stage heating/cooling), fan runs only in the 2nd stage: Commissioning ● ● ● Fan Valve Valve unit) Outputs used P350 = 4 (2nd stage) P201 = 5 (floor) P203 = 5 (fan coil ● ● ● M1 V1 V2 DC 0...10 V fan DC valve floor DC valve fan coil units RDG260KN See Technical data [➙ 137] for min. and max.
Connection Application examples Example 2: Swap and fan in the 2nd stage 6 2-pipe and 2-stage application with radiant heating/cooling panels, the fan only operates with the fan coil unit: ● Heating sequence: 1st panel and 2nd fan coil unit ● Cooling sequence: 1st fan coil unit and 2nd panel Commissioning ● Fan ● ● Valve Valve ● Swap Outputs used ● P350 = 6 (Cooling and 2nd stage heating) ● P201 = 5 (panel) ● P203 = 5 (fan coil unit) P254 = 1 M1 V1 V2 DC 0...
6 Connection Application examples Example 3: Swap and fan in the 2nd stage 2-pipe fan coil and 2-stage application with different types of equipment (On/Off control outputs), the fan only operates if output V1 is energized. Commissioning ● Fan ● Valve ● Valve Outputs used ● P350 = 5 (Heating and 2nd stage cooling) P201 = 2 (equipment ● 1) P203 = 2 (equipment ● 2) M1 V1 V2 DC 0...
Technical data 7 7 Technical data Power supply (RDG200KN) Operating voltage (L-N) AC 24 V ±20 % or AC 230 V +10/-15 % (selectable via slider) Frequency 50/60 Hz Power consumption 4 VA @ AC 24 V 7 VA @ AC 230 V ● No internal fuse! External preliminary protection with max. C 10 A circuit breaker required in all cases. ● Before switching on power, select the right power supply needed using the power switch on the rear of the device.
7 Technical data Power supply (RDG260KN) Operating voltage (G-G0) DC 24 V: Make sure to connect G to + and G0 to - AC 24 V ±20 % DC 24 V ±2 V Frequency 50/60 Hz Power consumption 4 VA @ AC 24 V No internal fuse! External preliminary protection with max. C 10 A circuit breaker required for all cases.
Technical data 7 Multifunctional inputs X1-M/X2-M/U1-M Temperature sensor input Type NTC 3k Temperature range -20…70 °C Temperature sensor input Type LG-Ni1000 Temperature range -40…70 °C Digital input Operating action Selectable (NO/NC) Contact sensing DC 0…5 V, max.
7 Technical data Operational data Accuracy (after calibration via P007) <5% Humidity calibration range ±10 % Settings and display resolution Setpoint 0.5 °C Present temperature value displayed 0.5 °C Environmental conditions Storage IEC 60721-3-1 Climatic conditions Class 1K3 Temperature -25…65 °C Humidity < 95 % r.h. Transport IEC 60721-3-2 Climatic conditions Class 2K3 Temperature -25…65 °C Humidity < 95 % r.h.
Technical data 7 Standards and directives Eco design and labeling directives Based on EU directive 813/2013 (Eco design directive) and 811/2013 (Labelling directive) concerning space heaters, combination heaters, the following classes apply: RDG200KN ● Application with On/Off operation of Class I value 1 % a heater ● PWM (TPI) room thermostat, for use Class IV value 2 % with On/Off output heaters RDG260KN ● Application with On/Off operation of Class I value 1 % a heater ● PWM (TPI) room thermostat, for
7 Technical data Reference documentation Handbook for Home and Building Control - Basic Principles (https://my.knx.
Dimensions 8 8 Dimensions Dimensions in mm A6V11545892_en--_a 143 | 146
Index Index Numerics 1-speed .......................................................... 3-position control signal .................................... 3-speed .......................................................... 6-port ball valve ............................................... 83 75 83 72 A ACS tool ....................................................... 117 Adaptive temperature compensation .................. 58 Automatic heating/cooling changeover.......... 42, 54 B Basic application ........
Index Manually select heating or cooling sequence ...... 54 Minimum output............................................... 44 Moisture ......................................................... 53 Monitoring with ACS ...................................... 119 Monitoring with OZW772 ................................ 124 Multifunctional input ......................................... 88 N NFC ............................................................... 53 O On/Off control signal .........................
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.