User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functions
Fan control
4
88 | 150 A6V11545892_en--_a
● The output for the 1
st
stage (YHC1) in heating mode is also the 1
st
stage in
cooling
● This function is available for DC/3-speed/1-speed fans
We recommend enabling the swap function on applications with fan coil units and
floor heating/cooling. In this application, the fan runs during cooling demand (fan
coil unit and floor cooling) and only in the 2
nd
heating stage (with the fan coil unit).
Set P254 to On or Off, depending on the selected control signal (swap function),
and set P350 to 4 (fan in the 2
nd
stage).
The fan runs during heating demand and only in the 2
nd
cooling stage, e.g. for
applications with fan coil units and radiant heating/cooling panels.
This setting is available only when P350 is set to 5, and the swap function is
selected (P254 to On or Off).
Example 2:
P350=4
Example 3:
P350=5
Heating mode Cooling mode
● Swap function: The output for the 1
st
stage in heating mode is the 2
nd
stage for
cooling
● This function is available for DC/3-speed/1-speed fans
The following table shows the relation between fan behavior (switching range fan
XpH
Fan
/XpC
Fan
as per reference table or proportional band XpH/XpC) for
2-pipe / 2-stage applications depending on the selected output signals and
synchronization of the fan to the first or second sequence.
Combination
1
st
stage
signal
2
nd
stage
signal
Fan type Fan synchro Fan behavior
1 On/off On/off DC 1
st
sequence
XpH
Fan
/XpC
Fan
,
P-control
2 DC DC DC 1
st
sequence
XpH/XpC,
P/PI control
3 On/off On/off DC
2
nd
sequence
XpH
Fan
/XpC
Fan
,
P-control
4 DC DC DC
2
nd
sequence
XpH/XpC,
P/PI control
5 On/off DC DC 1
st
sequence
XpH
Fan
/XpC
Fan
,
P-control
Notes
Example 2
Example 3
Notes
Examples, other
combinations