User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functions
Control outputs
4
82 | 150 A6V11545892_en--_a
4.8.2 Control output configuration (setting via DIP switches 7/8 or
tool, and P201/P203/P204)
Application Fan Control outputs
Product
no.
DC 0...10 V 3-speed/
1-speed
Mod.
DC 0…10 V
On/Off
(2-pos)
On/Off
(3-wire)
Mod. PWM
(2-pos)
Mod.
3-pos.
RDG…KN
2-pipe ✓ ✓ ‒ ✓ ✓ ✓ ✓ 200
✓ ✓ ✓ ‒ ‒ ‒ ‒ 260
✓ ‒ ‒ ✓ ‒ ‒ ‒ 260
2-pipe with
electric heater
✓ ✓ ‒ ✓ ✓ ✓ ✓ 200
✓ ✓ ✓ ‒ ‒ ‒ ‒ 260
✓ ‒ ✓ ✓ ‒ ‒ ‒ 260
2-pipe with
radiator/floor
heating
✓ ✓ ‒ ✓ ✓ ✓ ✓ 200
✓ ✓ ✓ ‒ ‒ ‒ ‒ 260
✓ ‒ ✓ ✓ ‒ ‒ ‒ 260
2-pipe/2-stage,
cooling or
heating
✓ ✓ ‒ ✓ ✓ ✓ ✓ 200
✓ ✓ ✓ ‒ ‒ ‒ ‒ 260
✓ ‒ ✓ ✓ ‒ ‒ ‒ 260
4-pipe ✓ ✓ ‒ ✓ ✓ ✓ ✓ 200
✓ ✓ ✓ ‒ ‒ ‒ ‒ 260
✓ ‒ ✓ ✓ ‒ ‒ ‒ 260
4-pipe with
electric heater
✓ ✓ ‒ ✓ ✓ ✓ ✓
1)
200
✓ ✓ ✓ ‒ ‒ ‒ ‒ 260
✓ ‒ ✓ ✓
2)
‒ ‒ ‒ 260
Heating / Cooling
with 6-port valve
‒ ‒ ✓ ‒ ‒ ‒ ‒ 260
Heating / Cooling
with 6-port valve
as changeover
and PICV valve
✓ ‒ ✓ ✓
3)
‒ ‒ ‒ 260
1)
Only available for cooling actuator
2)
Only selectable for electrical heater
3)
Relay outputs for 6-port valve as changeover
Note: On/off (2-pos) on RDG200.. are a triac outputs (max 1A), and relay outputs
(max 5(4)A) on RDG260..
Overview