User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Overview
Types
2
8 | 150 A6V11545892_en--_a
2 Overview
2.1 Types
For fan coil units, universal applications and compressors in DX-type equipment
applications
Product no. Stock no.
Operating
voltage
Fan Number of control outputs
Built-in
sensor
3-speed DC On/Off PWM 3-pos DC
On/Off
(3-wire)
Humidity,
temperature
RDG200KN S55770-T409
AC 24 V or
AC 230 V
✓ ✓
1)
3 3 2 ‒ 2 ✓
RDG260KN S55770-T412
AC 24 V or
DC 24 V
✓ ✓
1)
‒ ‒ ‒ 3 ‒ ✓
‒ ✓
1)
2
2)
‒ ‒ ‒ ‒
1)
The terminal Y50 is used as DC 0…10 V output.
2)
The output is relay On/Off.
2.2 Functions
The RDG2..KN KNX room thermostats are designed for use with the following:
Fan coil units via On/Off or modulating/DC control outputs:
● 2-pipe system
● 2-pipe system with electric heater
● 2-pipe system with radiator/floor heating
● 2-pipe/2-stage system
● 4-pipe system
● 4-pipe system with electric heater
● 4-pipe system with PICV and 6-port ball valve as changeover (RDG260KN)
Chilled/heated ceilings (or radiators) via On/Off or modulating/DC control outputs:
● Chilled/heated ceiling
● Chilled/heated ceiling with electric heater
● Chilled/heated ceiling and radiator/floor heating
● Chilled ceiling and radiator/floor heating
● Chilled/heated ceiling/2-stage
● Chilled/heated ceiling (4-pipe) with 6-port ball valve (RDG260KN)
● Chilled/heated ceiling with PICV and 6-port ball valve as changeover
(RDG260KN)
Compressor applications via On/Off control:
● Heating or cooling, compressor in DX-type equipment
● Heating or cooling, compressor in DX-type equipment with electric heater
● Heating and cooling, compressor in DX-type equipment
● Heating or cooling/2-stage, compressor in DX-type equipment
Control application