User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Func
tions
Control sequences
4
76 | 150 A6V11545892_en--_a
4.7.12 Setpoints and sequences
In changeover applications, the Comfort setpoints for heating and cooling
sequence are the same (w).
In 2-pipe applications with electric heater, the Comfort setpoint is either at the first
heating sequence (in heating mode) or at the cooling sequence (in cooling mode).
In 2-pipe applications with radiator, the Comfort setpoint is either at the radiator
sequence (in heating mode) or at the cooling sequence (in cooling mode).
The setpoints for Economy and Protection are below the Comfort setpoints (for
heating) and above the Comfort setpoints (for cooling).
They can be set via P019, P020 (Economy) and P100, P101 (Protection).
Application Comfort mode Economy/Protection mode
Heating Cooling Heating Cooling
2-pipe
2-pipe with
electric heater
2-pipe with
radiator
2-pipe/
2-stage
heating or
cooling
1)
If P027 = On
W = Setpoint in Comfort mode
W
HeatEco/Prot
= Setpoint heating in Economy or Protection mode
W
CoolEco/Prot
= Setpoint cooling in Economy or Protection mode
YR = Radiator sequence
YE = Electric heater sequence
2-pipe applications