User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
About this document
Target audience, prerequisites
1
A6V11545892_en--_a 7 | 150
1.3.4 Document user/request to the reader
Before using products from Siemens Industry, Inc., it is important that you read the
documents supplied with or ordered at the same time as the products (equipment,
applications, tools, and so on) carefully and in full.
We assume that persons using our products and documents are authorized and
trained appropriately and have the technical knowledge required to use our
products as intended.
More information on the products and applications is available:
● On the intranet (Siemens employees only) at
https://wse04.siemens.com/content/P0002723/SitePages/Home.aspx
● From the Siemens branch office near you
www.buildingtechnologies.siemens.com or from your system supplier
● From the support team at headquarters fieldsupport-zug.ch.sbt@siemens.com
if there is no local point of contact
Siemens assumes no liability to the extent allowed under the law for any losses
resulting from a failure to comply with the aforementioned points or for the
improper compliance of the same.
1.4 Target audience, prerequisites
This document assumes that users of the RDG2..KN room thermostats are familiar
with the ETS tool, Synco ACS tool or both and can use them.
It is also assumed that these users are aware of the specific conditions associated
with KNX.
In most countries, specific KNX know-how is conveyed through training centers
certified by the KNX Association (see www.knx.org/).
For reference documentation, see Reference documents [➙ 5].
1.5 Glossary
The inputs, outputs and parameters of an application can be influenced in various
ways. These are identified by the following symbols in this document:
Parameters identified by this symbol are set using ETS.
Parameters identified by this symbol are set using ACS.
Note!
Setting RDG2..KN KNX parameters is only supported by the
following tool versions:
● ETS5 or higher versions
● ACS version 13.03 or higher
Inputs and outputs identified by this symbol communicate with
other KNX devices.
They are called communication objects (CO).
The communication objects of the RDG2..KN works partly in S-
Mode, partly in LTE-Mode, and partly in both. These objects are
described accordingly.
A list of the parameters is shown in Control parameters [➙ 108].