User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functions
Control sequences
4
A6V11545892_en--_a 65 | 150
T[°C]
Room temperature
w Room temperature setpoint
YHC1 Control command "Stage 1"
YHC2 Control command "Stage 2"
SDH
Switching differential "Heating"
(P051)
SDC Switching differential "Cooling"
(P053)
w
D
Setpoint differential (P056)
The diagrams below show the control sequence for modulating PI control.
Heating mode (P001 = 0) Cooling mode (P001 = 1)
Changeover (P001 = 2 or P001 = 3,
P254 = 0)
Changeover (P001 = 2 or P001 = 3,
P254 = 1) (swap function)
T[°C] Room temperature
w Room temperature setpoint
YHC1 Control command "Stage 1"
YHC2 Control command "Stage 2"
XpH Proportional band "Heating"
(P050)
XpC Proportional band "Cooling"
(P052)
w
D
Setpoint differential (P056)
The diagrams only show the PI thermostat’s proportional part.
For setting sequence and control outputs, see Application overview [➙ 37],
Sequence overview (setting via P001) [➙ 56] and Control outputs [➙ 78].
● For applications with different signals, On/Off (1
st
stage) and DC (2
nd
stage),
heating/cooling P-band modulating (P050, P052), a small switching differential
SDH / SDC (P051, P053) is suggested to start 1
st
sequence as soon as heating
/ cooling demand is requested.
● Set the heating flow limitation function with parameter P256 (RDG260KN)
when using a PICV in this application. See Additional functions [➙ 42].
Modulating control:
3-position, PWM or
DC 0…10 V
Note
Note