In this case, an electric heater is connected directly to outputs Q2 (RDG260KN),
and the current heats up the relay contact. This falsifies the internal temperature
sensor reading. The thermostat compensates the temperature, if the rated power
of the electric heating is entered at P217.
Factory setting P217: 0.0 kW, setting range: 0.0…1.2 kW.
The diagrams below show the control sequence for On/Off control.
Heating mode
(changeover = heating or heating only)
Cooling mode
(changeover = cooling or cooling only)
The diagrams below show the control sequence for modulating control.
Heating mode
(changeover = heating or heating only)
Cooling mode
(changeover = cooling or cooling only)
The diagrams only show the PI thermostat’s proportional part.
For setting sequence and control outputs, see Application overview [ 37],
Sequence overview (setting via P001) [ 56] and Control outputs [ 78].
Parameter P256 (RDG260KN) sets the heating flow limitation when using a PICV.
See Additional functions [ 42].
On/Off control
Control sequence
On/Off output
Modulating control:
3-position, PWM or
DC 0…10 V
Control sequence
modulating control output