User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functions
Room temper
ature setpoints
4
36 | 150 A6V11545892_en--_a
● Local and central shifts are added up
● Applies only to Comfort and Economy setpoints; Protection setpoints are not
shifted centrally
● The current setpoint heating and cooling is limited by the Protection setpoint. If
the Protection setpoint is Off, both the minimum 5 °C and maximum 40 °C are
used
● The current setpoints for cooling and heating of the same operating mode have
a minimum distance of 0.5 K
● The result of local and central shifting, together with room operating mode,
humidity control or setpoint tracking for cooling, is used by the thermostat for
temperature control (current setpoint)
● The room thermostat always takes over the setpoints received from the
controller RMB795B. Thus, the setpoints adjusted locally on the thermostats
are overridden by the setpoints from the room group (e.g., every 15 minutes)
– On RMB, the circumstances under which the controller sends out the
setpoints can be defined. Refer to CE1P3122 for "Setpoint priority" and
"Setpoint Master" functions
Setpoint priority
Setpoint master (RMB)