User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functions
Operating modes
4
A6V11545892_en--_a 31 | 150
Application for "Window contact", "Presence detector" and “Central time schedule”
In Room 3, the time schedule is between 13:00 and 17:00.
● In the morning, as soon as presence is detected, the operating mode switches
to Comfort (1)
● The users open the window briefly and the operating mode switches to
Protection (2)
● In the afternoon, the central time schedule sets Comfort mode from 13:00 to
17:00 (3)
● After 17:00, the room is still occupied, and the operating mode remains in
Comfort (occupancy via presence detector) (4)
● The users open the window and exit the room for a short time. The operating
mode switches to Protection as long as the window is open (5)
● As soon as the room is unoccupied, the thermostat switches to Economy (6)
● After this time, occupancy detected by the presence detector has no effect, and
the central time schedule sets the thermostat to Protection (7)
Example 3