User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Func
tions
Operating modes
4
A6V11545892_en--_a 29 | 150
4.2.2 Communication examples
The following examples show 3 typical applications for a central time schedule
together with local control of the room operating mode.
The room operating mode in rooms 1…3 of a building is determined by the time
schedule. Window contacts are installed in all rooms.
The following conditions are specified:
The rooms are used and controlled by the time schedule as follows:
● Night setback from 17:00 to 08:00 (Economy)
● Lunch break from 12:00 to 13:00 (Pre-Comfort)
The substitution (P910) for Pre-Comfort via bus is set on the thermostats as
follows:
● Room 1: Comfort (1)
● Room 2: Economy (0)
Window contact
In Room 1, the window is opened briefly, once in the morning and once in the late
afternoon (1). The opening in the morning and afternoon directly influences the
actual room operating mode.
During lunch break (2), the time schedule changes to Pre-Comfort. The mode
remains in Comfort as set by parameter "Transformation Pre-Comfort" (P910 = 1).
Example 1