- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functions
Operating modes
4
A6V11545892_en--_a 27 | 150
The operating mode can be changed to Comfort or Economy based on room
occupancy (room occupied or unoccupied, via presence detector or keycard).
For details, see Presence detector [➙ 45]
Comfort mode can be temporarily extended (e.g., working after business hours or
on weekends) when the thermostat is in Economy mode.
1. Press the operating mode button to return to Comfort for the preset period
(P102).
2. Press the operating mode button again to stop the schedule.
The following conditions must be fulfilled:
● Room is unoccupied (via bus)
or
mode selection via operating mode button is set to "Auto (Comfort)-Protection"
(P002 = 1) or "Auto (Comfort)-Protection Hospitality" (P002 = 3) and the time
schedule via bus is Economy
● P102 (extend Comfort period) is greater than 0
During the temporary Comfort mode extension, symbol displays.
When P102 (extend Comfort period) equals 0, extended Comfort cannot be
activated; pressing the left button will switch the thermostat to Protection.
If the operating mode window contact is active, press the left button and OFF
displays (blinking).
The actual room operating mode can be forced temporarily to Comfort or
Economy/Protection. The time period is adjusted via the rotary knob:
● Extend presence: Set the thermostat to Comfort for the selected time
● Extend absence: Set the thermostat to Economy/Protection for the selected
time
To activate the function, press and hold the left button and, within 3 seconds, turn
the rotary knob…
● clockwise for extended presence
● counterclockwise for extended absence
The rotary knob adjusts the time period:
● Extend presence: 0:00…+9:30 in steps of 30 minutes; the symbol is
displayed
● Extend absence: 0:00…–9:30 in steps of 30 minutes; the symbol or is
displayed
During the extended presence/absence periods, symbol is displayed.
Presence detector
Temporary timer to extend
Comfort mode
Timer to extend
presence/absence