User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Connection
Application examples
6
A6V11545892_en--_a 139 | 150
2-pipe fan coil and 2-stage application with different types of equipment (On/Off
control outputs), the fan only operates if output V1 is energized.
Commissioning Outputs used
● Fan P350 = 5 (Heating
and 2
nd
stage cooling)
● Valve P201 = 2 (equipment
1)
● Valve P203 = 2 (equipment
2)
● M1 DC 0...10 V fan (2
nd
stage)
● V1 On/Off valve
(equipment 1)
● V2 On/Off valve
(equipment 2)
See Technical data [➙ 140] for min. and
max. ratings
RDG260KN
Example 3:
Swap and fan in the 2
nd
stage