User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Connection
Application examples
6
138 | 150 A6V11545892_en--_a
2-pipe and 2-stage application with radiant heating/cooling panels, the fan only
operates with the fan coil unit:
● Heating sequence: 1
st
panel and 2
nd
fan coil unit
● Cooling sequence: 1
st
fan coil unit and 2
nd
panel
Commissioning Outputs used
● Fan P350 = 6 (Cooling
and 2
nd
stage heating)
● Valve P201 = 5 (panel)
● Valve P203 = 5 (fan coil
unit)
● Swap P254 = 1
● M1 DC 0...10 V fan
(2
nd
stage)
● V1 DC valve panel
● V2 DC valve fan coil
unit
See Technical data [➙ 140] for min. and
max. ratings
RDG260KN
Example 2:
Swap and fan in the 2
nd
stage