User Manual

Table Of Contents
Connection
Application examples
6
A6V11545892_en--_a 133 | 150
2-pipe fan coil application for dehumidification, with DC 0...10 V fan and DC valve
(without temperature setpoint shifting):
Commissioning Outputs used
Fan P351 = 3
(or DIP6 = OFF)
Control strategy P450 = 1
Setpoint high P024 = 50 %
(factory setting)
Temp. shift P461 = 0
Valve P201 = 5
Relay function P402 = 7
(dehumidifier)
M1 DC 0...10 V fan
V1 DC valve
L3
*)
Dehumidifier
*)
Release contact
See Technical data [ 140] for min. and
max. ratings
RDG260KN
4-pipe fan coil application for dehumidification, with temperature setpoint shifting,
dehumidifier contact, DC 0...10 V fan and On/Off valves:
Commissioning Outputs used
Fan P351 = 3
(or DIP6 = OFF)
Control strategy P450 = 1
Setpoint high P024 = 50 %
(factory setting)
Temp. shift P461 = 3 K
(factory setting)
Valve P201/P203 = 4
Relay function P402 = 7
(dehumidifier)
M1 DC 0...10 V fan
V1, V2 On/Off valves
L3
*)
Dehumidifier
*)
Release contact
See Technical data [ 140] for min. and
max. ratings
RDG260KN
Example 2:
Dehumidifier,
DC 0...10 V fan + valve,
No shifting setpoint
Example 3:
Dehum./DC 0...10 V fan,
On/Off valves