User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Connection
Application examples
6
132 | 150 A6V11545892_en--_a
6.3 Application examples
The examples are described for RDG260KN, but they also apply to RDG200KN.
Control output (P201, P204) and terminals for the valves (Y1, Y2) need to be
adapted accordingly.
6.3.1 Humidity control
In the following examples, P461 is configured based on the connected type of
equipment. See details in Humidity [➙ 52].
2-pipe fan coil application for dehumidification, with temperature setpoint shifting
and dehumidifier contact, DC 0...10 V fan and DC valve:
Commissioning Outputs used
● Fan P351 = 3
(or DIP6 = OFF)
● Control strategy P450 = 1
● Setpoint high P024 = 50 %
(factory setting)
● Temp. shift P461 = 3 K
(factory setting)
● Valve P201 = 5
● Relay function P402 = 7
(dehumidifier)
● M1 DC 0...10 V fan
● V1 DC valve
● L3
*)
Dehumidifier
*)
Release contact
See Technical data [➙ 140] for min. and
max. ratings
RDG260KN
Note:
Example 1: Dehumidifier,
DC 0...10 V fan and valve