User Manual

Table Of Contents
Connection
Connection diagrams
6
130 | 150 A6V11545892_en--_a
RDG260KN DC 0…10 V fan 1-speed/3-speed fan
Application V1 V2 V3
2-pipe YHC
Terminals
Q1 Q2 Y10 Y20 Y30 Y50 Q1 Q2 Q3 Y10 Y20 Y30
Control outputs: DC V1 V1
On/Off
V1
2-pipe with radiator
4-pipe
2-pipe/2-stage
YHC
YH
YHC1
YR
YC
YHC2
Terminals
Q1 Q2 Y10 Y20 Y30 Y50 Q1 Q2 Q3 Y10 Y20 Y30
Control outputs: DC DC V1 V2 V1 V2
DC
On/Off V2 V1
On/Off
DC
V1 V2
On/Off On/Off V1 V2
2-pipe with electric
heater
YHC YE
Terminals
Q1 Q2 Y10 Y20 Y30 Y50 Q1 Q2 Q3 Y10 Y20 Y30
Control outputs: DC DC V1 V2 V1 V2
DC
On/Off
V2 V1
On/Off
DC
V1 V2
On/Off On/Off V1 V2
4-pipe with electric
heater
YH YC YE
Terminals Q1 Q2 Y10 Y20 Y30 Y50 Q1 Q2 Q3 Y10 Y20 Y30
Control outputs: DC DC DC V1 V2 V3 V1 V2 V3
DC DC On/Off V3 V1 V2
N1 Room thermostat RDG260KN M1 1-speed or 3-speed fan, DC 0…10 V fan
S1, S2, S3 Switch (keycard, window contact, presence
detector etc.)
V1, V2, V3 Valves actuators:
On/Off or DC 0...10 V, heating, cooling,
radiator, heating/cooling, 1
st
or 2
nd
stage
YE Electric heater B1, B2, B3 Temperature sensor (return air temperature,
external room temperature, changeover
sensor, etc.)
YH Heating valve actuator DH Dehumidifier
Q3=On/Off, Y50=0…10 V
YC Cooling valve actuator YHC Heating/cooling valve actuator
CE+ KNX data + YR Radiator valve actuator
CE- KNX data - YHC1/YHC2 1
st
/2
nd
stage