User Manual

Table Of Contents
Connection
Connection diagrams
6
A6V11545892_en--_a 129 | 150
6.2 Connection diagrams
RDG200KN DC 0…10 V fan 1-speed/3-speed fan
Application V1 V2 V3
2-pipe YHC
Terminals Y1 Y3 Y2 Y4 Y50 Q1 Q2 Q3 Y1 Y3 Y2 Y4
Control outputs: 2-pos
(PWM)
V1 V1
3-pos V1 V1 V1 V1
2-pipe with radiator
4-pipe
2-pipe/2-stage
YHC
YH
YHC1
YR
YC
YHC2
Terminals
Y1 Y3 Y2 Y4 Y50 Q1 Q2 Q3 Y1 Y3 Y2 Y4
Control outputs:
2-pos
(PWM)
2-pos
(PWM)
V1 V2 V1 V2
2-pos
(PWM)
3-pos
V1 V2 V2 V1 V2 V2
3-pos 2-pos
(PWM)
V1 V1 V2 V1 V1 V2
3-pos 3-pos V1 V1 V2 V2 V1 V1 V2 V2
2-pipe with
electric heater
YHC YE
Terminals Y1 Y3 Y2 Y4 Y50 Q1 Q2 Q3 Y1 Y3 Y2 Y4
Control outputs: 2-pos
(PWM)
2-pos
(PWM)
V1 V2 V1 V2
2-pos
(PWM)
3-pos
V1 V2 V2 V1 V2 V2
3-pos 2-pos
(PWM)
V1 V1 V2 V1 V1 V2
3-pos 3-pos V1 V1 V2 V2 V1 V1 V2 V2
4-pipe with
electric heater
YH YC YE
Terminals Y1 Y2 Y4 Y3 Y50 Q1 Q2 Q3 Y1 Y2 Y4 Y3
Control outputs: 2-pos
(PWM)
2-pos
(PWM)
2-pos
(PWM)
V1 V2 V3 V1 V2 V3
2-pos
(PWM)
3-pos 2-pos
(PWM)
V1 V2 V2 V3 V1 V2 V2 V3
N1 Room thermostat RDG200KN M1 1-speed or 3-speed fan, DC 0…10 V fan
S1, S2, S3 Switch (keycard, window contact, presence
detector etc.)
B1, B2, B3 Temperature sensor (return air temperature,
external room temperature, changeover
sensor, etc.)
V1, V2, V3 Valve actuators:
On/Off or PWM, 3-position, heating, cooling,
radiator, heating/cooling, 1
st
or 2
nd
stage
YH Heating valve actuator
YE Electric heater YC Cooling valve actuator
K Relay YHC Heating/cooling valve actuator
CE+ KNX data + YR Radiator valve actuator
CE- KNX data - YHC1/YHC2 1
st
/2
nd
stage