User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functi
ons
Control parameters
4
114 | 150 A6V11545892_en--_a
Parameter
Name
Factory setting
Range
RDG200KN
RDG260KN
Dependencies
Expert level
Inputs
P150 Input X1 P150:1
P153: 0
P155: 3
0 = --- (no function)
1 = Room temp ext. sensor / return (AI)
2 = H/C changeover (AI/DI)
3 = Window contact [PROT] (DI)
4 = Dewpoint sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)(DI)
8 = Monitor input (Temp) (AI)
9 = Supply air sensor (AI)
10 = Presence detector / card reader (DI)
11 = External temperature limit (AI)
12 = Coil temperature (AI)
13 = Hotel presence detector / card
reader (DI)
✓ ✓ P153:
P150,
P155
P155:
P150,
P153
P153 Input X2
P155 Input U1
P151 Normal position and sensor input
X1
0 when DI or
AI/DI
2 when AI
0 = Normally Open
1 = Normally Close
2 = NTC-3K
3 = LG-Ni1000
✓ ✓ P151:
P150
P154:
P153
P156:
P155
P154 Normal position and sensor input
X2
P156 Normal position and sensor input
U1
Outputs
P200
4)
Number of heating / cooling
sequences
Note: for 2-/4-pipe 2-stage
application
1 1 = 2 sequence heating, 2 sequence
cooling
2 = 2 sequence heating, 1 sequence
cooling
3 = 1 sequence heating, 2 sequence
cooling
✓ ✓ d01
P201
RDG20xKN: Output Y1 (and Y3 for
3-pos)
RDG26xKN: Output Y10 (DC) or Q1
(2-pos)
RDG200KN:
4
RDG260KN:
5 (6 when
application
type is 4-pipe
with 6-port
ball valve)
1 = 3-position ✓ ‒ ‒
2 = On/Off 3 wires ✓ ‒ ‒
3 = PWM ✓ ‒ ‒
4 = On/Off ✓ ✓ ‒
5 = DC ‒ ✓ ‒
6 = 6-port valve (DC 0… 10 V) ‒ ✓ Appl
7 = 6-port valve (DC 2… 10 V) ‒ ✓ Appl
8 = Inverse signal, 6-port valve (DC
10…0 V)
‒ ✓ Appl
9 = Inverse signal 6-port valve (DC 10…
2 V)
‒ ✓ Appl
P203 RDG20xKN: Output Y2 (and Y4 for
3-pos)
RDG26xKN: Output Y20 (DC) or Q2
(2-pos)
RDG200KN:
4
RDG260KN:
5
1 = 3-position ✓ ‒ ‒
2 = On/Off 3 wires ✓ ‒ ‒
3 = PWM ✓ ‒ ‒
4 = On/Off ✓ ✓ ‒
5 = DC ‒ ✓ ‒
P204 RDG20xKN: Output Y3
RDG26xKN: Output Y30 (DC)
RDG200KN:
4
RDG260KN:
5
3 = PWM ✓ ‒ ‒
4 = On/Off ✓ ✓ ‒
5 = DC ‒ ✓ ‒