User Manual

Table Of Contents
Functions
Control parameters
4
A6V11545892_en--_a 113 | 150
4.15.5 Expert level parameters with diagnostics and test
Parameter
Name
Factory setting
Range
RDG200KN
RDG260KN
Dependencies
Expert level
Control settings
P050 Heat P-band Xp 2 K 0.5…6 K
P051 Switching differential heating 1 K 0.5…6 K
P052 Cool P-band Xp
P053 Switching differential cooling
P054 Radiator P-band Xp/switching
differential
2 K 0.5…6 K
P055 Dead zone Comfort mode 2 K 0.5…5 K
P056 Setpoint differential 2 K 0.5…5 K
P057
1)
Integral action time Tn for heating 45 min 0...120 min P201,
P203,
P204
P058
1)
Integral action time Tn for cooling
P059
2)
H/C changeover switching point
cooling
16 °C (61 °F) 5 °C…P060-2 K (41 °F…P060-2 K) P001,
P150,
P153,
P155
P060
2)
H/C changeover switching point
heating
28 °C (82 °F) P059+2 K…40 °C (P059+2 K…104 °F)
P001,
P150,
P153,
P155
P063 Minimum supply air temperature OFF OFF, 0 °C…P064 (32 °F…P064)
P150,
P153,
P155
P064 Maximum supply air temperature OFF OFF, P063…50 °C (P063…122 °F) P150,
P153,
P155
Mode and setpoints
P100 Protection heating setpoint 8 °C (46 °F) OFF, 5 °C…P101; (41 °F…P101)
P101 Protection cooling setpoint OFF OFF, P100…40 °C; (P100…104 °F)
P102
3)
Temporary Comfort mode OFF OFF, 1...360 min P002
P103 Temporary Comfort setpoint OFF 0 = Disabled (OFF)
1 = Enabled (ON)
2 = Enabled (ON), excluded Window
contact
3 = Enabled (ON), excluded presence
detector (include hotel presence)
P104 Setpoint display 1 1 = Absolute setpoints
2 = Relative setpoints
P110 Energy indicator 1 OFF = Disabled
1 = Green and Red dimmed out
2 = Green dimmed out / Red fixed
3 = Green and Red fixed
P111 Energy indicator range 2 K 0…10 K