User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functions
Control parameters
4
A6V11545892_en--_a 113 | 150
4.15.5 Expert level parameters with diagnostics and test
Parameter
Name
Factory setting
Range
RDG200KN
RDG260KN
Dependencies
Expert level
Control settings
P050 Heat P-band Xp 2 K 0.5…6 K ✓ ✓ ‒
P051 Switching differential heating 1 K 0.5…6 K ✓ ✓ ‒
P052 Cool P-band Xp
P053 Switching differential cooling
P054 Radiator P-band Xp/switching
differential
2 K 0.5…6 K ✓ ✓ ‒
P055 Dead zone Comfort mode 2 K 0.5…5 K ✓ ✓ ‒
P056 Setpoint differential 2 K 0.5…5 K ✓ ✓ ‒
P057
1)
Integral action time Tn for heating 45 min 0...120 min ✓ ✓ P201,
P203,
P204
P058
1)
Integral action time Tn for cooling
P059
2)
H/C changeover switching point
cooling
16 °C (61 °F) 5 °C…P060-2 K (41 °F…P060-2 K) ✓ ✓ P001,
P150,
P153,
P155
P060
2)
H/C changeover switching point
heating
28 °C (82 °F) P059+2 K…40 °C (P059+2 K…104 °F) ✓ ✓
P001,
P150,
P153,
P155
P063 Minimum supply air temperature OFF OFF, 0 °C…P064 (32 °F…P064) ✓ ✓
P150,
P153,
P155
P064 Maximum supply air temperature OFF OFF, P063…50 °C (P063…122 °F) ✓ ✓ P150,
P153,
P155
Mode and setpoints
P100 Protection heating setpoint 8 °C (46 °F) OFF, 5 °C…P101; (41 °F…P101) ✓ ✓ ‒
P101 Protection cooling setpoint OFF OFF, P100…40 °C; (P100…104 °F) ✓ ✓ ‒
P102
3)
Temporary Comfort mode OFF OFF, 1...360 min ✓ ✓ P002
P103 Temporary Comfort setpoint OFF 0 = Disabled (OFF)
1 = Enabled (ON)
2 = Enabled (ON), excluded Window
contact
3 = Enabled (ON), excluded presence
detector (include hotel presence)
✓ ✓ ‒
P104 Setpoint display 1 1 = Absolute setpoints
2 = Relative setpoints
✓ ✓ ‒
P110 Energy indicator 1 OFF = Disabled
1 = Green and Red dimmed out
2 = Green dimmed out / Red fixed
3 = Green and Red fixed
✓ ✓ ‒
P111 Energy indicator range 2 K 0…10 K ✓ ✓ ‒