User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-pipe/2-stage heating or cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.13 Communication objects (S-Mode)
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index /
Functions
Control parameters
4
A6V11545892_en--_a 111 | 150
4.15.4 Service level parameters
Parameter
Name
Factory setting
Range
RDG200KN
RDG260KN
Dependencies
Service level
P001 Control sequence
1)
2-pipe:
1 = Cooling
only
4-pipe:
4 = Heating
and cooling
0 = Heating only
1 = Cooling only
2 = H/C changeover auto
3 = H/C changeover manual
4 = Heating and cooling
✓ ✓ P002
P002 Operation via room operating mode
selector
1)
1 1 = Auto (Comfort) – Protection
2 = Auto - Comfort - Economy -
Protection
3 = Auto (Comfort) - Protection
Hospitality
✓ ✓ P001
P003 Operation via fan operating selector
2)
0 0 = Auto - Manual
1 = Manual
2 = Auto - Manual - Protection
3 = Auto – Protection
✓ ✓ P350
P004 Unit 0 0 = °C (parameter in °C)
1 = °F (parameter in °F)
✓ ✓ ‒
P006 Measured value correction 0 K –5…5 K
✓ ✓ ‒
P007 Humidity value correction 0 -10…0…10 %
✓ ✓ ‒
P008 Standard display 0 0 = Room temperature
1 = Setpoint
✓ ✓ ‒
P009 Additional display information 0 0 = --- (No display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12 h) (via bus)
4 = Time of day (24 h) (via bus)
5 = Humidity
✓ ✓ ‒
P010 Setpoint concept 1 1 = Comfort concept
2 = Energy saving concept
✓ ✓ P104
P011 Comfort basic setpoint 21 °C (70 °F) 5…40 °C (41…104 °F)
✓ ✓ ‒
P013 Comfort setpoint minimum 5 °C (41 °F) (P010 = 1): 5 °C (41 °F)...P016-1 K
(P010 = 2): 5 °C (41 °F)...P014-1 K
✓ ✓ P010
P014 Comfort setpoint maximum heating 21 °C (70 °F) P013+1 K…P015-1 K
✓ ✓ P010
P015 Comfort setpoint minimum cooling 25 °C (77 °F) P014+1 K…P016 -1 K
✓ ✓ P010
P016 Comfort setpoint maximum 35 °C (95 °F) (P010 = 1): P013 +1 K...40 °C
(104 °F)
(P010 = 2): P015 +1 K...40 °C
(104 °F)
✓ ✓ P010
P019 Economy heating setpoint 15 °C (59 °F) OFF (0), 5 °C…P020 (41 °F…P020)
P020 = 40 °C max. (P020 = 104 °F
max.)
✓ ✓ ‒
P020 Economy cooling setpoint 30 °C (86 °F) OFF (0), P019…40 °C
(P019…104 °F)
P019 = 5 °C min. (P019 = 41 °F min.)
✓ ✓ ‒
P024 Humidity setpoint high 50 OFF (0), P026 or 20…90 %
✓ ✓ P450