Obj Object name Function Type/
length
Flags Obj Object name Function Type/
length
Flags
53 Fan output 0…100 % 5.001
1 byte
CRT 65 Heating, control
value status
Off
On
1.011
1 bit
CRT
Indicates the current fan speed as a value 0...100 %.
Speed Fan output (physical KNX
value)
Indicates the control status of heating actuator of the first stage
OFF 0 % (0) 66 Heating, control
value status seq 2
Off
On
1.011
1 bit
CRT
1 33 % (84)
2 66 % (186) Indicates the control status of heating actuator of the second
stage.
3 100 % (255)
54
55
56
Fan speed 1
(receive)
Fan speed 2
(receive)
Fan speed 3
(receive)
Off
On
1.001
1 bit
CWU 67 Cooling, control
value status
Off
On
1.011
1 bit
CRT
The fan can be set to a specified speed by a KNX control unit
when manual fan operation is enabled.
Indicates the control status of cooling actuator of the first stage.
57
58
59
Fan speed 1
(send)
Fan speed 2
(send)
Fan speed 3
(send)
Off
On
1.001
1 bit
CRT 68 Cooling, control
value status seq 2
Off
On
1.011
1 bit
CRT
Indicates the control status of cooling actuator of the second
stage.
Indicate the state of the relay outputs. 69 Heating and
cooling, control
value status
Off
On
1.011
1 bit
CRT
60 Outside
temperature
Temperature 9.001
2 bytes
CWU
The outside temperature measured by a KNX sensor can be
displayed on the thermostat, if P009 "Additional display
information" is set to 2 (outside temperature).
Indicates the control status of heating and cooling actuator of the
first stage.
70 Heating and
cooling, control
value status seq2
Off
On
1.011
1 bit
CRT
61 Heating, control
value continuous
0…100 % 5.001
1 byte
CRT Indicates the control status of heating and cooling actuator of the
second stage.
Indicates the position of the heating actuator of the first stage.
E.g., 2-pipe with electric heater application: Output of heating coil.
71 Heating and
cooling, control
value continuous
0…100 % 5.001
1 byte
CRT
62 Heating, control
value continuous,
seq 2
0…100 % 5.001
1 byte
CRT
Indicates the position of the heating and cooling actuator of the
first stage.
Indicates the position of the heating actuator of the second stage.
E.g., 2-pipe with electric heater application: Output of the electric
heater.
72 Heating and
cooling, control
value continuous
seq 2
0…100 % 5.001
1 byte
CRT
63 Cooling, control
value continuous
0…100 % 5.001
1 byte
CRT Indicates the position of the heating and cooling actuator of the
second stage.
Indicates the position of the cooling actuator of the first stage.
E.g., 2-pipe with electric heater application: Output of the cooling
coil.
73 Control
dehumidification
Off
On
1.011
1 bit
CRT
64 Cooling, control
value continuous,
seq 2
0…100 % 5.001
1 byte
CRT Indicates the control status of the dehumidification.
74 Control
humidification
Off
On
1.011
1 bit
CRT
Indicates the position of the cooling actuator of the second stage.
E.g., 2-stage changeover application: Output of the second
cooling stage.
Indicates the control status of the humidification.