Coil temperature sensor
External temperature limit
Hotel presence detector
Selectable relay functions
Switching off external equipment during Protection mode
Switching on external equipment (e.g. pump) during heating/cooling demand
Output status heating/cooling sequence
Dehumidification/humidification control output
KNX communication features
KNX bus (terminals CE+ and CE-) for communication with Synco devices or KNX
compatible devices
Display of outside temperature or time of day from KNX bus
Time scheduling and central control of setpoints from KNX bus
Control of Economy setpoints via KNX bus
Relative humidity setpoint via KNX bus
Control of KNX actuators and fan via S-Mode objects
Energy supply optimization via energy demand signal via Synco™ RMB795B central
control unit
Interworking with Siemens AQR.. and QMX.. sensors for room humidity and room
temperature measurement
Interworking with Siemens QMX.. room operator units for room humidity, room
temperature and operating commands for fan, operating mode and setpoints
Power supply selection for RDG200KN
The RDG200KN can be powered either on AC 230 V (default) or AC 24 V.
To select the correct power supply, use the power switch on the rear of the device.
Note:
The outputs (triacs and relays) follow the main power supply, either AC 230 V or AC 24 V.
The device will be damaged if set to AC 24 V, but powered on AC 230 V.
Applications
The RDG2..KN room thermostats support the following applications, which can be
configured using the DIP switches on the rear of the unit or via the commissioning tool.
Remote configuration
Set DIP switches 15 to Off (remote configuration, factory setting) to select an application
via commissioning tool.
Remote configuration via commissioning tool (factory setting)
Synco
TM
ACS
ETS
Commissioning via Siemens smartphone application PCT Go
for Android
TM
ON =
DIP NO.: 1…5
OFF =
DIP NO.: 1…5