User Manual

17
Siemens
Datasheet
A6V11545853_en--_a
Smart Infrastructure
2020-09-07
Scan the antenna area without powering on the thermostat.
Scan the NFC area without unpacking the thermostat from the individual box.
Antenna area
Unpowered thermostat from individual
package
Notes
Each time the application is changed, the thermostat reloads the factory settings for all
control parameters excepting KNX device and zone addresses.
The commissioning via Siemens smartphone application PCT Go for Android™ can be
disabled via parameters to avoid unexpected changes of the thermostat.
Connect tools
Connect the Synco ACS or ETS tools to the KNX bus cable at any point for
commissioning.
ACS and ETS require an interface:
KNX interface (e.g. Siemens N148…)
OCI702 USB-KNX interface
Control sequence
Set the control sequence via parameter P001 depending on the application. Factory setting:
Application
Factory setting P001
2-pipe and chilled/heated ceiling, and 2-stage
1 = Cooling only
4-pipe, chilled ceiling and radiator,
6-port ball valve applications
4 = Heating and cooling
Calibrate sensor
Recalibrate the temperature sensor if the room temperature displayed on the thermostat
does not match the room temperature measured (after min. 1 hour of operation). To do this,
change parameter P006.