User Manual
11
Siemens
Datasheet
A6V11545853_en--_a
Smart Infrastructure
2020-09-07
Type of unit
Product no.
Datasheet
*)
Electrothermal actuator, AC 24 V, NC,
DC 0…10 V, 1 m
STA63
4884
Electrothermal actuator, AC 24 V, NO,
DC 0…10 V, 1 m
STP63
4884
Rotary actuators for ball valves AC 24 ,
DC 0…10 V
GDB161.9E
4657
KNX actuators
Type of unit
Product no.
Datasheet
*)
Rotary actuators for ball valves KNX S-Mode
GDB111.9E/KN
A6V10725318
*)
The documents can be downloaded from http://siemens.com/bt/download
1)
With PWM control, exact parallel run of 2 or more thermal actuators is not possible . If
several fan coil units are controlled by the same room thermostat, motorized actuators with
On/Off or 3-position control are preferred.
Note:
For more information about parallel operation and the max. number of actuators that can be
used, refer to the data sheets of the selected actuator type and the following list:
Max. number of actuators in parallel on RDG200KN (AC 230 V):
● 6 SS..31.. actuators (3-position)
● 4 ST..23.. if used with On/Off control signal
● 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
● Parallel operation of SAS31 not available
Max. number of actuators in parallel on RDG200KN (AC 24 V):
● 6 SS..81.. actuators (3-position)
● 4 ST..73.. if used with On/Off control signal
● 2 SFA71.. On/Off actuators
● Parallel operation of SAS81 not available
Max. number of actuators in parallel on RDG260KN (AC 24 V):
● 10 SS..61.. actuators (DC)
● 10 ST..23/63/73.. actuators (DC or On/Off)
● 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
● 10 SAS61.. actuators (DC)
● 10 GDB161.9E