Technical data
48 / 60
Siemens RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation CE1P3076.en
Building Technologies Functions 19 Jun 2009
P52 Fan operation 1 0 = disabled
1 = enabled
2 = heating only
3 = cooling only
P53 Fan speed 3-speed 1 = 1-speed
2 = 3-speed
P54 Fan overrun time
(only when electrical heater is used)
60 s 0...360 s
P55 Switching point fan speed high 100% 80..100%
P55 ECM fan max. output ECM: 80% ECM: fan min…100%
P56 Switching point fan speed medium 65% 30...75%
P56 ECM fan min. output ECM: 30% ECM: 0%...fan max.
P57 Switching point fan speed low 10% 1...15%
P57 ECM: Switching point fan ECM:10% ECM: 0..100%
P58 Fan start booster ON ON: Enabled
OFF: Disabled
P59 Fan min. on time 2 min. 1...6 min
P60 Fan kick interval in Comfort mode
(time until next kick)
0 0…89 min, OFF (90 min.)
P61 Fan kick interval in E-saving mode
(time until next kick)
OFF 0…359 min, OFF (360 min. )
P62 Clean filter reminder running time Off (0) OFF, 100…9900 hours
P65 Protection heating setpoint 8 °C OFF, 5…W Cool Prot;
(W Cool Prot = 40 °C max.)
P66 Protection cooling setpoint OFF OFF, W Heat Prot…40;
(W Heat Prot = 5 °C min.)
P67 Fan start delay in 2P control 0 s 0...180 s
P68 Extension Comfort period OFF OFF; 15...360 min
P69 Temporary setpoint Comfort mode
(see also Comfort setpoint P08)
OFF OFF = disabled
ON = enabled
P70 Infrared receiver ON OFF = disabled
ON = enabled
P71 Reload factory settings OFF OFF = disabled
ON = reload start
Parameter
Name Factory setting Range
RDG100
RDG100T
RDG110
RDG140
RDG160
Dia
g
nostics and test
d01 Application type Diagnostics 0 = (no application)
1 = 2-pipe
2 = 2-pipe with electrical heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2 stage heating or cooling
6 = 4-pipe with electrical heater
d02 X1 status Diagnostics 0 = not activated (for DI)
1 = activated (DI)
0…49 °C = cur temp value (for AI)
00 = H/C input closed
100 = H/C input open
d03 X2 status Diagnostics 0 = not activated (for DI)
1 = activated (DI)
0…49 °C = cur temp value (for AI)
00 = H/C input closed
100 = H/C input open
d04 D1 status Diagnostics 0 = not activated (for DI)
1 = activated (DI)
00 = H/C input closed
100 = H/C input open
d05 Test mode for checking
actuator direction Y1/Y2
(press left button to escape)
--- “---“ = no signal at outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing
d06 Test mode for checking
actuator direction Y3/Y4
(press left button to escape)
--- “---“ = no signal at outputs Y3 and Y4
OPE = output Y3 forced opening
CLO = output Y4 forced closing
Parameter available