Technical data
46 / 60
Siemens RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation CE1P3076.en
Building Technologies Functions 19 Jun 2009
4.15.1 Parameters of the "Service level"
Parameter
Name Factory setting Range
RDG100
RDG100T
RDG110
RDG140
RDG160
Service level
P01 Control sequence With 2-pipe /
2-stage:
1 = cooling only
With 4-pipe:
4 = H/C
0 = heating only
1 = cooling only
2 = H/C changeover manually
3 = H/C changeover automatically
4 = heating or cooling
P02 Operating mode profile (operating mode button) 1 1 = (Auto) - Comfort - Protection
2 = (Auto) - Comfort - E-saving - Prot
P03 Fan mode selection 0 0 = Auto - Manual
1 = Manual
2 = Auto - Manual - Prot
P04 Selection of °C or °F 0 (°C) 0 = degrees Celsius (°C)
1 = degrees Fahrenheit (°F)
P05 Sensor calibration (internally, externally) 0 K – 3...3 K
P06 Standard temperature display 0 0 = room temperature
1 = setpoint
P07 Display info line
(2nd line of LCD)
0 0 = --- (no display)
1 = °C and °F
0..1
0..1 0..1 0..1
P08 Comfort setpoint 21 °C 5...40 °C
P09 Min. setpoint for Comfort mode 5 °C 5...40 °C
P10 Max. setpoint for Comfort mode 35 °C 5...40 °C
P11 Energy Saving heating setpoint 15 °C OFF, 5 ... WcoolE-saving;
(WcoolE-saving = 40 °C max.)
P12 Energy Saving cooling setpoint 30 °C OFF, WHeatE-saving ... 40 °C;
(WHeatE-saving = 5 °C min.)
P13 Electrical heater in cooling mode ON ON: Enabled
OFF: Disabled
P14 Button lock function 0 0 = unlocked
1 = auto locked
2 = manual locked