Technical data

30 / 60
Siemens RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation CE1P3076.en
Building Technologies Functions 19 Jun 2009
Modulating control: 3-position or PWM
The diagrams below show the control sequence of modulating PI control.
Heating mode with manual selection (P01=2) Cooling mode with manual selection P01=2)
Y [%]
100
0
w
3181D1124
T[°C]
XpH
Y1
Y2 (YE)
w
D
½ SDH ½ SDH
3181D105
Y [%]
100
0
w
T[°C]
Y3
XpC
Heating and cooling mode (P01=4)
T[°C] Room temperature
w Room temperature setpoint
Y2 Control. command “El. heater"
(only on/off)
Y1 Control command “Valve” or “Comp.” (H)
(only PWM, not 3-position)
Y3 Control command “Valve” or “Comp.” (C)
XpH Proportional band “Heating” (P30)
XpC Proportional band “Cooling” (P31)
X
dz
Dead zone (P33)
Y [%]
100
0
w
3181D114
T[°C]
Y3
XpH
Y1
XpC
½
x
dz
½
x
dz
Y2 (YE)
w
D
½ SDH ½ SDH
w
D
Setpoint differential (P34)
The diagrams only show the PI controller’s proportional part.
Setting the sequence and the control outputs
Refer to sections 4.5 ("Applications"), 4.7.1 ("Sequences") and 4.7.2 ("Outputs").
Y1 can only be on/off or PWM
Y2 can only be on/off
Y3 can be on/off, PWM or 3-position
Note
Notes