s RDG1… RDG100T Room thermostats with display, for fan coil units RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation Edition: 1.
Contents 1 About this document ..............................................................................4 1.1 Revision history.........................................................................................4 1.2 Reference documents ...............................................................................4 1.3 1.3.1 1.3.2 1.3.3 Before you start .........................................................................................4 Copyright ......................................
5 Handling.................................................................................................49 5.1 Mounting and installation ........................................................................49 5.2 Operation ................................................................................................50 5.3 Disposal ..................................................................................................52 6 Engineering ...............................................
1 About this document 1.1 Revision history Edition Date Changes Section 1.1 1.0 June 2009 May 2009 Several small corrections First edition All 1.2 Pages Reference documents Ref. Document title Type of document Document no. [1] [2] Wall-mounted room thermostats with LCD RDG1… Data Sheet Operating Instructions CE1N3181en CE1B3181.1en [3] RDG100T Operating Instructions CE1B3181.2en [4] RDG100, RDG100T Mounting Instructions CE1M3181.
1.3.3 Document use / request to the reader Before using our products, it is important that you read the documents supplied with or ordered at the same time as the products (equipment, applications, tools, etc.) carefully and in full. We assume that persons using our products and documents are authorized and trained appropriately and have the technical knowledge required to use our products as intended.
2 Summary 2.1 Brief description Applications • 2-pipe fan coil units, 2-pipe with electrical heater, 2-pipe with radiator / floor heating • 4-pipe fan coil units, 4-pipe with electrical heater • 2-stage heating or cooling application • Compressors in dx type equipment • Universal heating and/or cooling Features, all types • 2 multifunctional inputs and 1 digital input for keycard contact, external sensor, etc.
• Advanced fan control function, i.e. fan kick, fan start, selectable fan operation (enable, disable or depending on heating or cooling mode) • Purge function together with 2-port valve in a 2-pipe changeover system • Reminder to clean filters • Floor heating temperature limit • Reloading factory settings for commissioning and control parameters • 7-day time program: 8 programmable timers to switch over between Comfort and Energy Saving mode (RDG100T) • Infrared remote control (RDG100T) 2.
2.3 Equipment combinations Product no. Data Sheet IRA211 3059 Cable temperature sensor QAH11.1 1840 Room temperature sensor QAA32 1747 QXA2000 / AQX2000 1542 MVI…/MXI… 4867 Electromotoric ON/OFF actuator SFA21... 4863 Thermal actuator (for radiator valves) STA21... 4877 STP21... 4878 SUA… 4832 SSA31... 4893 SSP31… 4864 SSB31... 4891 SSD31... 4861 SQS35… 4573 SSA61... 4893 SSC61… 4895 SSP61… 4864 SSB61... 4891 SSD61...
2.4 Accessories Description Changeover mounting kit (50 pcs / package) Adapter plate 120 x 120 mm for 4“ x 4“ conduit boxes Adapter plate 112 x 130 mm for surface wiring 2.5 Product no. ARG86.3 Data Sheet 1840 ARG70 ARG70.2 Ordering When ordering, please indicate product no. and description: E.g. RDG100 room thermostat Order the IRA211 infrared remote control separately. Order valve actuators separately.
General note 4 Functions 4.1 Temperature control Setting of the control parameters (P01, etc., mentioned throughout the document) is described in section 4.15. The thermostat acquires the room temperature via built-in sensor, external room temperature sensor (QAA32), or external return air temperature sensor (QAH11.1), and maintains the setpoint by delivering actuator control commands to heating and/or cooling equipment.
4.2 Operating modes Select the thermostat's operating mode via the operating mode button on the unit or operating mode input (e.g. keycard occupancy sensor), when X1, X2, or D1 is set to 3 (P38, P40, P42). A corresponding setpoint is used to maintain the room temperature at the desired level depending on the active operating mode. The following operating modes are available: Comfort mode In Comfort mode, the thermostat maintains the room temperature setpoint which can be adjusted via the rotary knob.
4.3 Room temperature setpoints Comfort mode The setpoint in Comfort mode can be adjusted via the rotary knob. Setpoint limitation For energy saving purposes, the setpoint setting range can be limited to minimum (P09) and maximum (P10). P09 < P10 • If the minimum limit P09 is set lower than the maximum limit P10, both heating and cooling are adjustable between these 2 limits P09 ≥ P10 • For heating or cooling applications (e.g.
4.4 Setpoints and sequences 4.4.1 2-pipe and 2-stage applications On changeover applications, the Comfort setpoints for heating and cooling sequence are the same (w). On 2-pipe applications with electrical heater, the Comfort setpoint is either at the first heating sequence (in heating mode) or at the cooling sequence (in cooling mode). On 2-pipe applications with radiator, the Comfort setpoint is either at the radiator sequence (in heating mode) or at the cooling sequence (in cooling mode).
4.4.2 4-pipe applications On 4-pipe applications, the Comfort setpoint (w) is in the middle of the dead zone, between the heating and cooling sequence. The dead zone can be adjusted via parameter P33. If manual changeover is selected, then either the cooling sequence or the heating sequence is released. In this case, the Comfort setpoint is at the selected heating or cooling sequence.
4.5 Applications overview The thermostats support the following applications, which can be configured via DIP switches at the rear of the unit. Depending on the type of thermostat, on/off or modulating control outputs are available. Application (set via DIP switches 1…3) Heating or cooling • 2-pipe fan coil unit • Chilled / heated ceiling • 1-stage compressor 1) DIP switch Control output (set via DIP swi. 4 and 5) ON/OFF, PWM, 3-position T Product no. RDG100..
1) Key Note 2) Heat pump application covered by RDG110 (SPDT = relay with NO and NC contact) With ECM fan control DC 0…10 V Y1 Y2 Heating or heating/cooling valve actuator Cooling valve actuator E1 Electrical heater M1 1-speed or 3-speed fan B1 Return air temperature sensor or external room temperature sensor (optional) B2 Changeover sensor (optional) The diagrams above only show the water-based fan coil applications, but not the compressor Universal applications The RDG1xx..
Purge function Caution The changeover sensor ensures changeover from heating to cooling mode based on the acquired water temperature. We recommend activating the purge function (parameter P50) with 2-port valves. This function ensures correct acquisition of the medium temperature even if the 2-port valve is closed for an extended period of time. The valve is then opened for 1 to 5 minutes (adjustable) at 2-hour intervals during off hours.
The table below shows the relation between parameter, temperature source and temperature display: External temp. sensor available Parameter P51 Source for display of room temperature Output control according to Floor temp. limit function OFF No Built-in sensor Built-in sensor Not active OFF Yes External temp. sensor External temp. sensor Not active 10...
If parameter P68 (extend Comfort period) = 0, extended Comfort cannot be activated; pressing the left button will show “OFF” (blinking 3 times). Temporary timer for extension of presence / absence The current operating mode can be forced temporarily into Comfort or Energy Saving / Protection mode.
4.7 Control sequences 4.7.1 Sequences overview (setting via parameter P01) The sequence can be set via parameter P01. The thermostats can be used in systems featuring: • • • • • Heating only (P01 = 0) Cooling only (P01 = 1) Manual heating / cooling changeover (P01 = 2) Automatic heating / cooling changeover (P01 = 3) Heating and cooling mode (e.g. 4-pipe system) (P01 = 4) The available modes depend on the application (selected via DIP switch, see section 4.5).
4.7.
4.7.3 2-pipe fan coil unit On 2-pipe applications, the thermostat controls a valve in heating / cooling mode with changeover (automatic or manual), heating only, or cooling only. Cooling only is factory set (P01 = 1). ON/OFF control The diagrams below shows the control sequence for 2-position control.
4.7.4 2-pipe fan coil unit with electrical heater Heating or cooling with auxiliary heater On 2-pipe applications with electrical heater, the thermostat controls a valve in heating / cooling mode with changeover, heating only, or cooling only plus an auxiliary electrical heater. Cooling only is factory set (P01=1) with enabled electrical heater (P13). Electrical heating, active in cooling mode In cooling mode, the valve receives an OPEN command if the acquired temperature is above the setpoint.
Modulating control 3-position, PWM or DC 0…10 V Control sequence modulating output The diagrams below show the control sequence for modulating control. Heating mode Cooling mode (automatic changeover = heating or heating only) (man. /auto.
4.7.5 2-pipe fan coil unit with radiator or floor heating Heating or cooling with radiator or floor heating On 2-pipe applications with radiator, the thermostat controls a valve in heating / cooling mode with changeover, heating only, or cooling only plus a radiator valve. Cooling only is factory-set (P01=1). Radiator, active in cooling mode In cooling mode, the valve receives an OPEN command if the acquired temperature is above the setpoint.
Modulating control: 3-position, PWM or DC 0…10 V The diagrams below show the control sequence for modulating PI control. Cooling mode (man. / auto.
4.7.6 4-pipe fan coil unit Heating and cooling On 4-pipe applications, the thermostat controls 2 valves in heating and cooling mode, heating / cooling mode by manual selection, or heating and cooling mode with changeover. Heating and cooling mode (P01=4) is factory-set. 4-pipe application with manual changeover The heating or cooling output can be released via operating mode button if parameter P01 is set to manual (P01=2).
The diagrams below show the control sequence for 2-position control. Heating mode with manual selection (P01=2) Y 3076D01 Y Cooling mode with manual selection (P01=2) Y1 3076D13 ON/OFF control Y2 1 1 w 0 T[°C] ½ SDC ½ SDC ½ SDH ½ SDH w 0 T[°C] Heating and cooling mode (P01=04) Y1 ½ xdz Y2 ½ xdz 3076D11 Y 1 w 0 ½ SDC ½ SDH T[°C] ½ SDC ½ SDH T[°C] Room temperature w Room temperature setpoint Y1 Control command “Valve” or “Comp.” (H) Y2 Control command “Valve” or “Comp.
4.7.7 4-pipe fan coil unit with electrical heater Heating and cooling with auxiliary heater On 4-pipe applications with electrical heater, the thermostat controls 2 valves in heating and cooling mode by manual selection, heating and cooling mode with automatic changeover, heating only, or cooling only plus an auxiliary electrical heater. Heating and cooling is factory-set (P01=4).
Modulating control: 3-position or PWM The diagrams below show the control sequence of modulating PI control. Y1 Y2 (YE) Y [%] 3181D1124 Y [%] Cooling mode with manual selection P01=2) 100 Y3 3181D105 Heating mode with manual selection (P01=2) 100 w 0 ½ SDH ½ SDH wD XpH w T[°C] 0 XpC T[°C] Y [%] Y1 Y2 (YE) Y3 ½ xdz ½ xdz 3181D114 Heating and cooling mode (P01=4) 100 T[°C] Room temperature w Room temperature setpoint Y2 Control. command “El.
4.7.8 2-stage heating or cooling 2-stage heating or cooling On 2-stage applications, the thermostat controls 2 valves or compressors in heating or cooling mode or changeover (automatic or manual). “Cooling only" is factory-set (P01=1). Heating mode In heating mode, the 1st stage is activated if the acquired temperature is below the setpoint. The 2nd stage is activated if the acquired room temperature drops below “setpoint” minus “setpoint differential”.
Modulating control: 3-position, PWM or DC 0…10 V The diagrams below show the control sequence of modulating PI control.
4.7.9 Chilled / heated ceiling and radiator applications For chilled / heated ceiling and radiator, • set the corresponding basic application • disable the fan (P52) The following applications are available: Application for chilled / heated ceiling, radiator Chilled / heated ceiling with changeover Chilled / heated ceiling & el. heater (cooling only: disable el. heater via P13) Chilled / heated ceiling & radiator 2-pipe See section 4.7.3 2-pipe & electrical heater 4.7.4 2-pipe & radiator 4.7.
ON OFF 1 2 3 C1 RV Hardware This application is available with RDG110 only. ON/OFF control The diagrams below show the control sequences for 2-position control.
4.8 Overview of control outputs Different control output signals are available depending on the thermostat type, the position of DIP switches 4 and 5, and parameters P46 and P47 (see section 4.7.2). Control output Product no. RDG100, RDG100T RDG110 Control outputs 2-position 2-position PWM 3-position Y1, Y2, Y3 (3 x N.O.
2. When the thermostat calculates the positions "fully close" or "fully open", the actuator's running time is extended + 150% to ensure the right actuator position is synchronized to the control algorithm. 3. After the actuator reaches the position calculated by the thermostat, a waiting time of 30 seconds is applied to stabilize the outputs. This function is available with RDG100 and RDG100T only.
4.9 Fan control Different fan output signals are available depending on the thermostat type: Overview of fan outputs Control output Product no. RDG100, RDG100T RDG110 RDG140 RDG160 On/off 1- / 3-speed fan Q1,Q2,Q3 (3) Q1,Q2,Q3 (3) Q1,Q2,Q3 (3) Modulating fan DC 0…10 V Y50 (1) ( ) Number of outputs The fan operates in automatic mode or at the selected speed with manual mode. In automatic mode, the fan speed depends on the setpoint and the current room temperature.
1-speed / 3-speed fan The thermostat can control a 1-speed or 3-speed fan (selected via control parameter P53). A 1-speed fan is connected to terminal Q1, a 3-speed fan to terminals Q1, Q2 and Q3. Control sequence for modulating fan (ECM fan) RDG160 has a DC 0…10 V output for electronically commutated (ECM) fan motors. The switching points can be set via parameter P55…P57.
Y 10385D22en Q1 0 t [h:mm] Periodic fan kick Minimum on-time Periodic fan kick Minimum on-time The periodic fan kick time can be selected individually for Comfort mode via parameter P60, and for Energy Saving mode via parameter P61. Note: Fan kick value “0” means the fan runs continuously in the dead zone. Fan kick value “OFF” means the fan does not run in the dead zone.
4.10 Multifunctional input, digital input The thermostat has 2 multifunctional inputs X1 and X2 and a digital input D1. A sensor type NTC like the QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals. The functionality of the inputs can be configured via parameters P38 for X1, P40 for X2, and P42 for D1.
4.11 Auto timer (RDG100T only) The thermostat provides an Auto Timer mode with 8 programmable timers. Each timer can be assigned to one or several days. In this mode, the thermostat automatically changes over between Comfort and Energy Saving mode according to the preprogrammed timers. Setting the time of day and the weekday 1. 2. 3. 12-hour and 24-hour format Press the program mode button to enter the programming mode menu. (OK) to enter the setting mode for the time of day.
The RDG100T provides 8 programmable timers A1 … A8. Each timer has a Comfort mode start and end time that can be applied to one or several weekdays. To set an auto timer, proceed as follows: Setting the timers 1. 2. 3. 4. 5. 6. Note View the programmable settings To save your adjustments, remember to press button (OK) in step 6 above before pressing button (Esc) to leave the programmable timer setting mode. You can view the 8 timers in sequence: 1. 2. 3.
Reloading the default timer settings 1. 2. 3. 4. Overlapping of timer sequences Press the program mode button twice to select the “Auto timer setting” programming mode. Press button (OK) to enter the timer setting mode. Press the program mode button for at least 3 seconds. “rES” will be displayed. Press button (OK) to confirm reloading of the default timer settings (Esc) to leave without change. or button The display will show “8888” during the reloading process.
4.14 DIP switches Use the DIP switches at the rear of the thermostat to commission the thermostat's basic application prior to snapping it to the base. ON OFF 1 2 3 4 5 – The application is set via DIP switches 1…3 – The function of the control outputs (2-position or 3-position) is set via DIP switches 4 and 5 for RDG 100 and RDG100T.
4.15 Control parameters A number of control parameters can be readjusted to optimize control performance. These parameters can also be set during operation without opening the unit. In the event of a power failure, all control parameter settings are retained. The control parameters are assigned to 2 levels: • “Service level”, and • “Expert level” with "Diagnostics and test" The “Service level” contains a small set of parameters to set up the thermostat for the HVAC system and to adjust the user interface.
RDG160 Range RDG140 Factory setting RDG110 Name RDG100T Parameters of the "Service level" RDG100 Parameter 4.15.1 0..1 0..1 0..
RDG140 RDG160 Range RDG110 Factory setting RDG100T Name Parameters of the "Expert level with diagnostics and test" RDG100 Parameter 4.15.2 0..6 0..6 0..6 0..6 0..6 0..6 0..6 0..6 0..6 0..6 0..6 0..6 0..6 0..6 0..6 Expert level P30 P-band / switching differential in heating mode 2K 0.5…6 K P31 P-band / switching differential in cooling mode 1K 0.5…6 K P32 P-band / switching differential for radiator 2K 0.5…6 K P33 Dead zone in Comfort mode 2K 0.
P52 Fan operation 1 0 = disabled 1 = enabled 2 = heating only 3 = cooling only P53 Fan speed 3-speed P54 60 s P55 Fan overrun time (only when electrical heater is used) Switching point fan speed high 1 = 1-speed 2 = 3-speed 0...360 s 100% 80..100% P55 ECM fan max. output ECM: 80% ECM: fan min…100% P56 Switching point fan speed medium 65% 30...75% P56 ECM fan min. output ECM: 30% ECM: 0%...fan max. P57 Switching point fan speed low 10% 1...
5 Handling 5.1 Mounting and installation Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the floor. Mounting • The room thermostat must be mounted in a clean, dry indoor place and must not be exposed to drip or splash water Wiring See Mounting Instructions (M3181) enclosed with the thermostat.
5.2 Operation See also Operating Instructions B3181 enclosed with the thermostat. Layout RDG100T RDG100 RDG110 RDG140 RDG160 1 3 2 4 3 4 1 2 3 4 Button operation 1 Operating mode button / Esc Button to enter the time and to set the timers Fan mode button / OK Rotary knob for setpoint and parameter adjustment • When the thermostat is in normal operation, the actual operating mode and status are indicated by symbols • When a button is pressed, the thermostat goes into mode selection.
24 23 22 LCD 21 20 19 18 17 1 2 3 16 4 15 5 14 6 8 8 9 # Symbol 10 11 7 12 13 Description # Symbol Description 1 Heating mode 14 Automatic fan 2 Electrical heater active 15 Manual fan 3 Cooling mode 4 Comfort mode 5 Energy Saving mode 6 Auto Timer mode 7 View and set auto timer program 8 Fan speed 1 16 Fan speed Fan speed 2 Fan speed 3 17 Degrees Celsius Degrees Fahrenheit Protection 18 Digits for room temperature and setpoint display 9 Escape 19 Button lock
5.3 Disposal The device is classified as waste electronic equipment in terms of the European Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules must be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 52 / 60 Siemens Building Technologies RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation Handling CE1P3076.
RDG100, RDG100T M 6 Engineering 6.1 Connection terminals L X1 X2 N Q1 Q2 Q3 L X1 N Q1 Q2 Q3 G X1 G0 L D1 GND L, N Operating voltage AC 230 V G, G0 Operating voltage AC 24 V SELV RDG110 M X2 D1 GND D1 GND SELV RDG140 M X2 SELV Q1 Q2 Q3 X1, X2 Multifunctional input for temperature sensor (e.g. QAH11.
6.2 Note Connection diagrams For details concerning connection of peripheral devices and setting of the DIP switches, please refer to the Mounting Instructions: – M3181.1 (RDG100, RDG100T) – M3181.2 (RDG110) – M3181.3 (RDG140, RDG160) RDG100… RDG110 1- or 3-speed fan 1- or 3-speed fan • 2-pipe • 2-pipe • 2-pipe & radiator • 4-pipe • 2-stage • 2-pipe & radiator • 4-pipe • 2-stage • 2-pipe & el. heater • 2-pipe & el. heater • 4-pipe & el. heater • 1 and 2-stage compressor • Compressor & el.
RDG140 RDG160 1- or 3-speed fan EMC fan DC 0…10 V S3 • 2-pipe • 2-pipe • 2-pipe & radiator • 4-pipe • 2-stage • 2-pipe & radiator • 4-pipe • 2-stage • 2-pipe & el. heater • 2-pipe & el. heater N1 M1 M2 V E1 YR Room thermostat RDG1… 1- or 3-speed fan EMC fan DC 0…10 V Valve actuators DC 0…10 V: Heating, cooling, radiator heating / cooling, 1st or 2nd stage Electrical heater DC 0…10 V controlled converter / current valve S1, S2 Switch (keycard, window contact, etc.
7 Mechanical design 7.1 General The room thermostat consists of 2 sections: • Plastic housing which accommodates the electronics, the operating elements and the temperature sensor • Mounting plate with the screw terminals The housing engages in the mounting plate and is secured with 2 screws on the left side. RDG100 RDG110 RDG140 RDG160 RDG100T For operation, refer to section 5.2. 7.2 Dimensions 3181M101 Dimensions in mm 56 / 60 Siemens Building Technologies RDG100…/RDG110…/RDG140...
8 Power supply Outputs Technical data Operating voltage Frequency Power consumption Fan control rating Q1, Q2, Q3-N RDG100, RDG100T, RDG110 AC 230 V +10/-15% 50/60 Hz Max. 18 VA AC 230 V, max. 5(4) A Y50 – G0 Control outputs Y1, Y2, Y3, Y4-N Y11-N / /Y21-N (N.O.) RDG140, RDG160 SELV AC 24 V ± 20% 50/60 Hz Max. 2 VA AC 230 V, max. 5(4) A (RDG140) SELV DC 0…10 V, max. ± 1mA (RDG160) AC 230 V, max. 1 A (RDG100, RDG100T) AC 230 V, max. 5(3) A (RDG110) SELV DC 0…10 V 39 mV Max.
Environmental conditions Standards Built-in room temperature sensor Measuring range Accuracy at 25 °C Temperature calibration range Settings and display resolution Setpoints Current temperature value displayed Operation Climatic conditions Temperature Humidity Transport Climatic conditions Temperature Humidity Mechanical conditions Storage Climatic conditions Temperature Humidity conformity EMC directive Low-voltage directive N474 0.5 °C 0.5 °C As per IEC 721-3-3 Class 3K5 0 …50 °C < 95% r.h.
Index 0 0…10 V DC 0…10 V......................................... 37 1 1- / 3-speed fan ..................................................... 37 12-hour and 24-hour format .................................. 41 1-speed fan............................................................ 38 3 3-position control signal......................................... 35 3-speed fan............................................................ 38 A Absence.................................................................
Operating voltage .................................................... 7 Overlapping of timer sequences............................ 43 P Parameter setting .................................................. 45 Power failure.......................................................... 41 Presence................................................................ 19 Programmable timers ............................................ 41 Proportional band ..................................................