Technical data

Living rooms:
Up to 26 °C for long-time presence, up to 28 °C for short-time presence.
Bath rooms:
Up to 28 °C for long-time presence, up to 30 °C for short-time presence.
The table below shows the relation between parameter, temperature source and
temperature display:
Parameter P51
External temp.
sensor available
Source for display of
room temperature
Output control
according to
Floor temp.
limit function
OFF
No
Built-in sensor
Built-in sensor
Not active
OFF
Yes
External temp. sensor
External temp. sensor
Not active
10...50 ˚C
No
Built-in sensor
Built-in sensor
Not active
10…50 ˚C Yes Built-in sensor
Built-in sensor + limit by
external sensor
Active
The "Floor temperature limitation" function influences the outputs listed in the table
below:
"Floor temp. limit" function has impact on
tt
Application Output Y1 Output Y2 Output Y3
Heating
(P01 = 0/2/3)
Cooling
(P01 = 1/2/3)
Heat. and cool
.
(P01 = 4) Remark
2-pipe H/C valve Y1 N/A
2-pipe & el heater
H/C valve El heater Y2 Y2 *) Only el heater
2-pipe & radiator H/C valve Radiator Y2 Y2 Only radiator
4-pipe Heating valve
Cooling valve
Y1 N/A Y1
4-pipe & el heater
Heating valve
Cooling valve
El. heater Y3 N/A Y3 Only el heater
2-stage 1st H/C 2nd H/C Y1, Y2 N/A
*) If P13 = ON electric heater in cooling mode
Either floor temperature sensor or external room temperature sensor can be used.
This function increases the comfort in the room by keeping the supply air
temperature of the fan coil unit between the selected minimum and maximum
temperature limits.
If the supply air temperature exceeds a limit, the thermostat reduces the
corresponding valve position until the supply air temperature is back in the limits.
In case the air flow is too low (especially with DC 0...10 V fans), this prevents cold
air from dumping into the room / warm air from bubbling straight up instead of
circulating.
To enable this function, the multifunctional input, to which the supply air sensor is
connected, needs to be set to "Supply air sensor" (e.g. P38=9). Then the
parameters for the limits are visible (P63: minimum supply air temperature,
P64: maximum supply air temperature).
This function is only active in Comfort mode and can only be used with DC 0...10 V
actuators.
For applications with electric heater, this function is not available.
Recommended values
for P51:
Note
Supply
air temperature
limitation (RDG160KN)
Note
30 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23