s Room thermostats with KNX communications RDG100KN, RDG160KN Basic Documentation Edition: 3.
Contents 1. About this document .............................................................................. 4 1.1 Revision history ......................................................................................... 4 1.2 Reference documents ............................................................................... 4 1.3 1.3.1 1.3.2 1.3.3 Before you start ......................................................................................... 5 Copyright ................................
.10 Handling faults ........................................................................................ 60 3.11 3.11.1 3.11.2 3.11.3 3.11.4 3.11.5 3.11.6 3.11.7 3.11.8 KNX communications .............................................................................. 60 S-mode.................................................................................................... 60 LTE mode ................................................................................................
1. About this document 1.1 Revision history Edition Date Changes Section 3.2 March 2014 3.1 Sept 2013 3.1 3.0 March 2013 January 2013 Various 2.4 4.1, 6.2, 8 8 8 8 2.4 various various various 2.0 June 2011 1.0 07 Jun 2010 • 2-position On/Off (only partially) • Update Equipment Combination • Protection via circuit breaker • Add eu.
1.3 Before you start 1.3.1 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.2 Quality assurance This document was prepared with great care.
1.4 Target audience, prerequisites This document assumes that users of the RDG KNX thermostats are familiar with the ETS and/or Synco ACS tools and able to use them. It also presupposes that these users are aware of the specific conditions associated with KNX. In most countries, specific KNX know-how is conveyed through training centers certified by the KNX Association (see www.knx.org/). For reference documentation, see section 1.2. 1.
Product no. RDG100KN RDG160KN 2. Summary 2.1 Types Stock no. S55770-T163 S55770-T297 Features Operating voltage AC 230 V AC 24 V Fan Number of control outputs On/Off 1) 3 2) 2 PWM 1) 2 3-pos. 1) 2 DC Backlit LCD 3-speed 2) 2 2 DC 3) 1) Selectable: On/Off, PWM or 3-position (triac outputs) 2) Either On/Off or DC control signal 3) 3-speed fan selectable only with DC outputs 2.
Features • Operating modes: Comfort, Economy and Protection • Automatic or manual heating / cooling changeover • Backlit display RDG100KN: • On/Off, PWM or 3-position control outputs (triac) • Output for 3-speed or 1-speed fan • AC 230 V operating voltage RDG160KN: • DC 0...10 V or On/Off control outputs for actuators • DC 0...
2.3 Integration via KNX bus The RDG room thermostats can be integrated as follows: • Integration into Synco 700 system via LTE mode (easy engineering) • Integration into Synco living via group addressing (ETS) • Integration into Desigo via group addressing (ETS) or individual addressing • Integration into third-party systems via group addressing (ETS) The following KNX functions are available: • Central time program and setpoints, e.g.
Synco topology Legend: Synco 700 Synco living RDG..., RDF…, RDU… OZW772 RMZ792 QAW... ACS RXB, RXL QAX Desigo and third-party systems Building automation and control system (BACS) Room automation and control system Room thermostats Web server Bus operator unit Room unit Service tool using OCI700.1 (OCI700.
2.4 On / off actuators Equipment combinations Description Product no. Data sheet Cable temperature or changeover sensor QAH11.1 1840 Room temperature sensor QAA32 1747 Condensation motion QXA2601 / QXA2602 / QXA2603 / QXA2604 3302 Electromotoric On/Off actuator SFA21... 4863 Electromotoric On/Off valve and actuator MVI… / MXI… 4867 SUA… 4832 STA23... *) 4884 *) STA73... *) 4884 *) STP23... *) 4884 *) STP73... *) 4884 *) SSA31... 4893 SSC31 4895 SSP31… 4864 SSB31...
Electromotoric actuator, DC 0...10 V (for valves 5.5 mm) SQS65… 4573 Electrothermal actuator, AC 24 V, NC, DC 0…10 V, 1 m STA63 4884 Electrothermal actuator, AC 24 V, NO, DC 0…10 V, 1 m STP63 4884 *) Note: With PWM control, it is not possible to ensure exact parallel running of 2 or more thermal actuators.
3. Functions 3.1 Temperature control General note: Parameters Setting of the control parameters (P01, etc., mentioned throughout the document) is described in section 3.14. Temperature control The thermostat acquires the room temperature via built-in sensor, external room temperature sensor (QAA32), or external return air temperature sensor (QAH11.1), and maintains the setpoint by delivering actuator control commands to heating and/or cooling equipment.
Note When an application program is downloaded to the Synco devices via ETS, the correct group addresses need to be downloaded as well, in order to display the time of day on the room thermostat (see Synco Knowledge Base - KB771). 3.2 Operating modes The thermostat's operating mode can be influenced in different ways (see below). Specific heating and cooling setpoints are assigned to each operating mode. KNX The thermostat sends the effective room operating mode on the bus.
3.2.1 Source for change of operating mode ACS Source Local operation via left button Bus command KNX R Room op. mode The operating mode can be influenced by different interventions. The source of the effective room operating mode state can be monitored using the "Cause" diagnostic data point in the ACS tool, operator unit RMZ792 or web server OZW772 / 775.
Auto Timer mode with time schedule via bus If a time schedule via bus is present, e.g. from central control unit, then the Auto Timer mode is active. The thermostat automatically changes between Comfort and Economy according to the time schedule via bus. The display shows the Auto Timer mode symbol along with the symbol for the effective room operating mode (Comfort or Economy ). By pressing the operating mode button, you can change to another operating mode.
Temporary timer to extend the Comfort mode Comfort mode can be temporarily extended (e.g. working after business hour or on weekends) when the thermostat is in Economy mode. The operating mode button switches the operating mode back to Comfort for the period preset in P68. Press the operating mode button again to stop the timer.
Function if no time schedule is received via bus User profile for operating mode (selected via P02) P02 = 1: P02 = 2: Note Operating mode when activating function Function Comfort Comfort Comfort or Economy Comfort or Economy Extension Absence Extension Absence Operating mode during function Comfort Protection Comfort Economy Operating mode at the end of function Protection Comfort Economy Comfort Extension / Absence functions not available in protection mode Function with time schedule via bus Use
3.2.2 Communication examples The following examples show two typical applications of a central time schedule in conjunction with local control of the room operating mode. The room operating mode in rooms 1…2 of a building is determined by the time schedule. Window contacts are fitted in all rooms.
Example 2 Interaction of user operation (operating mode button) and central time schedule In room 2, the window is opened briefly, once in the morning and once at night (1). Only the opening in the morning has a direct impact on the effective room operating mode. With the operating mode button, the operating mode can be changed between OFF and Auto or temporary Comfort extension respectively. • • • • Time schedule Room operating mode During lunch break, the time schedule changes to Precomfort.
Comfort mode 3.3 Room temperature setpoints 3.3.1 Description The factory setting for the Comfort basic setpoint is 21 °C and can be changed in the thermostat’s EEPROM via parameter P08 or via bus with communication object "Comfort basic setpoint". The last intervention always wins. The Comfort setpoint can be adjusted via the rotary knob, or via bus from a remote device like a touchpanel, operating unit, etc. The last intervention always wins.
*) Note: SW < V1.20 For heating and cooling applications (e.g. 4-pipe): – P09 is the setpoint for cooling and P10 the setpoint for heating – The setpoint can not be adjusted via the rotary knob Economy mode Use control parameters P11 and P12 to adjust the Economy mode setpoints. The heating setpoint is factory-set to 15 °C, and the cooling setpoint to 30 °C. Protection mode Use control parameters P65 and P66 to adjust the Protection mode setpoints.
3.3.
Clarification concerning current setpoint in Comfort mode The comfort setpoint w (e.g.
3.4 Applications overview The thermostats support the following applications, which can be configured using the DIP switches at the rear of the unit or a commissioning tool. Remote configuration DIP switches 1...3 need to be set to OFF (remote configuration, factory setting) to select an application via commissioning tool. Remote configuration, via commissioning tool (factory set) • Synco ACS • ETS DIP switches ON The tools provide the applications described in section 3.4.1 (basic applications).
Product no. RDG100KN RDG160KN RDG160KN Control outputs On/off, PWM, 3-position DC 0...10 V On/off 3.4.2 Fan 3-speed, 1-speed 3-speed, 1-speed, DC 0...10 V DC 0...
3.4.
3.5 Additional functions Heating / cooling changeover via bus The heating / cooling changeover information can be received via bus. This is only possible if the control sequence is set to automatic heating / cooling changeover (parameter P01 = 3) and no local input X1, X2, D1 is assigned with this function. KNX In the absence of the required information (e.g. due to problems with data communication, power failure, etc.
Manual heating / cooling changeover • Manual heating / cooling changeover means selection via changeover button on the thermostat by repeatedly pushing the button until the required mode is shown on the display (automatic changeover is done via bus or via an external sensor / switch connected to X1, X2, or D1).
Living rooms: Up to 26 °C for long-time presence, up to 28 °C for short-time presence. Bath rooms: Up to 28 °C for long-time presence, up to 30 °C for short-time presence. Recommended values for P51: The table below shows the relation between parameter, temperature source and temperature display: OFF OFF 10...50 ˚C External temp. sensor available No Yes No Source for display of room temperature Built-in sensor External temp.
Dew point monitoring Dew point monitoring is essential to prevent condensation on the chilled ceiling (cooling with fan disabled, parameter P52). It helps avoid associated damage to the building. A dew point sensor with a potential-free contact is connected to multifunctional input X1, X2 or D1. If there is condensation, the cooling valve is fully closed until no more condensation is detected, and the cooling output is disabled temporarily.
3.6 Control sequences 3.6.1 Sequences overview (setting via parameter P01) The main control sequence (i.e. the water coil sequence of the fan coil unit) can be set via parameter P01. The following sequences can be activated in the thermostats (each without or with auxiliary heating). The available sequences depend on the application (selected via DIP switch, see section 3.4). Parameter P01 = 0 P01 = 1 P01 = 2 P01 = 3 P01 = 4 T Sequence T °C T °C Heating Cooling = heating sequence for el.
3.6.2 KNX Application mode The behavior of the thermostat can be influenced by a building automation and control system (BACS) via bus with the command "Application mode". With this signal, cooling and/or heating activity can be enabled or disabled. Application mode is supported in LTE mode and S-mode.
ACS Heating OR cooling The state (heating or cooling) of the thermostat can be monitored with the ACS tool (diagnostic value "Control sequence"). The last active mode is displayed when the thermostat is in the dead zone or temperature control is disabled. With a 2 pipe application, the control sequence state is determined by the application mode (see section 3.6.
3.6.3 2-pipe fan coil unit On 2-pipe applications, the thermostat controls a valve in heating / cooling mode with changeover (automatically or manually), heating only, or cooling only. Cooling only is factory-set (P01 = 1). On/Off control The diagrams below show the control sequence for 2-position control.
3.6.4 2-pipe fan coil unit with electric heater Heating or cooling with auxiliary heater On 2-pipe applications with electric heater, the thermostat controls a valve in heating / cooling mode with changeover, heating only, or cooling only plus an auxiliary electric heater. Cooling only is factory-set (P01 = 1) with enabled electric heater (P13). Electric heating, active in cooling mode In cooling mode, the valve receives an OPEN command if the acquired temperature is above the setpoint.
On/Off control The diagrams below show the control sequence for 2-position. Heating mode Cooling mode (automatic changeover = heating or heating only) (man. / auto.
3.6.5 2-pipe fan coil unit with radiator or floor heating Heating or cooling with radiator or floor heating On 2-pipe applications with radiator, the thermostat controls a valve in heating / cooling mode with changeover, heating only, or cooling only plus a radiator valve. Cooling only is factory-set (P01 = 1). Radiator, active in cooling mode In cooling mode, the valve receives an OPEN command if the acquired temperature is above the setpoint.
Modulating control: 3-position, PWM or DC 0...10 V The diagrams below show the control sequence for modulating PI control.
3.6.6 4-pipe fan coil unit Heating and cooling On 4-pipe applications, the thermostat controls 2 valves in heating and cooling mode, heating / cooling mode by manual selection, or heating and cooling mode with changeover. Heating and cooling mode (P01 = 4) is factory-set. 4-pipe application with manual changeover The heating or cooling output can be released via operating mode button if parameter P01 is set to Manual (P01 = 2).
On/Off control The diagrams below show the control sequence for 2-position control.
3.6.7 4-pipe fan coil unit with electric heater (RDG100KN) Heating and cooling with auxiliary heater On 4-pipe applications with electric heater, the thermostat controls 2 valves in heating and cooling mode by manual selection, heating and cooling mode with automatic changeover, heating only, or cooling only plus an auxiliary electric heater. Heating and cooling is factory-set (P01 = 4).
Modulating control: 3-position or PWM The diagrams below show the control sequence of modulating PI control.
3.6.8 2-pipe / 2-stage heating or cooling 2-stage heating or cooling On 2-stage applications, the thermostat controls 2 valves or compressors in heating or cooling mode or changeover (automatically or manually). "Cooling only" is factory-set (P01 = 1). Heating mode In heating mode, the 1st stage is activated if the acquired temperature is below the setpoint. The 2nd stage is activated if the acquired room temperature drops below "setpoint" minus "setpoint differential".
Modulating control: 3-position, PWM or DC 0...10 V The diagrams below show the control sequence of modulating PI control.
3.6.9 Chilled / heated ceiling and radiator applications For chilled / heated ceiling and radiator, • set the corresponding basic application according to section 3.
3.6.11 Setpoints and sequences 2-pipe and 2-stage applications On changeover applications, the Comfort setpoints for heating and cooling sequence are the same (w). On 2-pipe applications with electric heater, the Comfort setpoint is either at the first heating sequence (in heating mode) or at the cooling sequence (in cooling mode). On 2-pipe applications with radiator, the Comfort setpoint is either at the radiator sequence (in heating mode) or at the cooling sequence (in cooling mode).
4-pipe applications On 4-pipe applications, the Comfort setpoint (w) is in the middle of the dead zone, between the heating and cooling sequence. The dead zone can be adjusted via parameter P33. If manual changeover is selected, then either the cooling sequence or the heating sequence is released. In this case, the Comfort setpoint is at the selected heating or cooling sequence.
Overview of control outputs 3.7 Control outputs 3.7.1 Overview Different control output signals are available. They need to be defined during commissioning (see below). Control output Product no. RDG100KN RDG160KN On/Off control signal (2-position) On/Off PWM 3-position DC 0…10 V Y1, Y2, Y3 (3 x NO) Q1, Q2, (2 x NO) Y1, Y3, (2 x PWM) --- Y1/Y2, Y3/Y4 (2 x / ) --- --Y10, Y20 The valve receives the OPEN/ON command via control output Y1 (Q1 on RDG160KN) or Y3 (Q2 on RDG160KN) when… 1.
Synchronization 1. When the thermostat is powered up, a closing command for the actuator running time + 150% is provided to ensure that the actuator fully closes and synchronizes to the control algorithm. 2. When the thermostat calculates the positions "fully close" or "fully open", the actuator's running time is extended + 150% to ensure the right actuator position is synchronized to the control algorithm. 3.
G FF G Y N1 Y E PWM AC 24 V G0 Y1 G 3181D21 L F... U1 DC 0 ... 10 V Y1 G L Q G0 Y1 K... 5.7 kW max. N1 U1 Y1 K… FF F… RDG160KN Signal converter SEM61.4 (see Data Sheet N5102) Current valve SEA45.1 (see Data Sheet N4937) Safety loop (e.g. safety thermostat and hightemperature cutout) Very fast-acting fuse Overcurrent trip N 3.7.2 Control outputs configuration (setting via DIP switches 4/5 or tool, and parameters P46/P47) Control outputs Overview Mod. PWM Mod. 3-pos. Mod.
RDG100KN The type of the control outputs (2- or 3-position) is set via DIP switches 4 and 5. The patterns of DIP switches 4 and 5 are as follows: OFF OFF 1 Y1/Y2 = Y3/Y4 = Notes: 2 3 4 5 2-position 2-position ON ON OFF OFF 1 2 3 4 5 2-position 3-position 3181D101 ON ON 1 2 3 4 5 3-position 2-position 1 2 3 4 5 3-position 3-position • If 2-position is selected, the factory setting is On/Off. If you want PWM (pulse width modulation), set parameters P46 and/or P47 to 2 = PWM.
3.8 Overview fan outputs Fan control Different fan output signals are available depending on the thermostat type: Control output Product no. RDG100KN RDG160KN On/off 1- / 3-speed fan Q1,Q2,Q3 (3) 1) Q1,Q2,Q3 (3) Modulating fan DC 0…10 V Y50 (1) 1) Control type selected via P53 P53, DIP 4 ( ) Number of outputs 1) Selectable via P53 or DIP switch 4 on RDG160KN The fan operates in automatic mode or at the selected speed with manual mode.
The individual switching points for ON of each fan stage can be adjusted via control parameters P55…P57. The fan speed switch off point is 20% below the switch on point. The diagrams below show fan speed control for modulating PI control. 3-speed fan control with modulating heating / cooling control (PWM, 3-pos or DC 0...
1-speed / 3-speed fan The thermostat can control a 1- or 3-speed fan (selected via control parameter P53). A 1-speed fan is connected to terminal Q1, a 3-speed fan to terminals Q1, Q2 and Q3. Control sequence for DC 0...10 V fan (ECM) and DC 0...10 V valves (RDG160KN) When DC 0...10 V Fan and DC 0...10 V valve output control are selected, the fan switching points can be set via the following parameters: – P55: ECM fan max. output – P56: ECM fan min.
Fan kick P60, P61 In automatic fan mode and with the room temperature in the dead zone, the control valve is normally closed and the fan disabled. With the "Fan kick" function, the fan can be released from time to time at low speed for minimum on-time (see above) even if the valve is closed. This function can be used to avoid damage from moisture due to a lack of air circulation, or to allow a return air temperature sensor to acquire the correct room temperature.
Clean fan filter reminder The "Clean fan filter reminder" function counts the fan operating hours and displays message "FIL " to remind the user to change / clean the fan filter as soon as the threshold is reached. This does not impact the thermostat's operation, which continues to run normally. The function is set via parameter P62 (default = Off (0)). KNX The "Clean filter reminder" is reset when the operating mode is manually set to Protection and back.
3.9 Multifunctional input, digital input The thermostat has 2 multifunctional inputs X1 and X2 and a digital input D1. An NTC type sensor like the QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals. The functionality of the inputs can be configured via parameters P38 + P39 for X1, P40 + P41 for X2, and P42 + P43 for D1. KNX The current temperature or state of the inputs X1/X2 and D1 is available on bus for monitoring purposes.
# 6 KNX Function of input Fault Description DI Monitor input (Digital) R 8 Monitor input (Temperature) Sensor input to monitor the state of an external sensor (e.g. QAH11.1) via bus. AI -- R 9 Supply air temperature limitation (RDG160KN only) Sensor input to acquire the supply air temperature. The thermostat controls the room temperature via the built-in sensor. The control output (DC 0...10 V) is reduced if the supply air temperature exceeds the min / max limits (P63, P64).
3.10 Handling faults Temperature out of range When the room temperature is outside the measuring range, i.e. above 49 °C or below 0 °C, the limiting temperatures blink, e.g. "0 °C" or "49 °C". In addition, the heating output is activated if the current setpoint is not set to "OFF", the thermostat is in heating mode and the temperature is below 0 °C. For all other cases, no output is activated. The thermostat resumes Comfort mode after the temperature returns to within the measuring range.
RDG Time Switch Geogr. zone 2.5.1 or 2.1.1 Geogr. zone 2.5.1 Room temperature Operating mode Operating mode Chiller Refr. distr zone 1 Refr. distr zone 1 Cool demand Cool demand Boiler Heat distr zone 1 Heat distr zone 1 Heat demand Heat demand Sensor Outside temperature zone 31 Outside temperature Engineering and commissioning Outside temperature zone 31 Outside temperature • For a detailed description of KNX (topology, bus supply, function and setting of LTE zones, filter tables, etc.
The zones to be defined are as follows: Geographical zone (space zone) Zone in which an RDG KNX thermostat is physically located. Other room-specific devices may also be located in this zone. (Apartment . Room . Subzone) Apartment = ---, 1...126 Room = ---, 1...63 Subzone = fix 1 Information exchanged in this zone is related specifically to the device like operating mode, setpoints, room temperature, etc. The designations "Apartment", "Room" and "Subzone" do not need to be taken literally.
3.11.4 Example of heating and cooling demand zone The building is equipped with Synco controls on the generation side and RDF / RDG thermostats on the room side. Konnex TP1 RMH760 Controller 1 RMB795 Controller 3 Controller 2 RDF... Controller 4 RDU... Controller 5 RDG...
3.11.5 Send heartbeat and receive timeout In a KNX network, S-mode and LTE mode communication objects can be exchanged between individual devices. The Receive timeout defines the period of time within which all the communication objects requested from a device must have been received at least once. If a communication object is not received within this period, a predefined value is used.
3.11.8 Fault function on KNX If a fault occurs (e.g. digital fault input, dew point, communication configuration, etc.) then a fault will be sent on the bus. An RDG thermostat listens on the bus and sends its fault when the fault has the highest alarm priority. This ensures that the management station does not miss any alarms. If alarms occur at the same time, the alarm with the highest priority will be first displayed and sent on the bus.
3.12 Communication objects (S-mode) 3.12.
3.12.2 Description of communication objects Obj 1 Object name System time Function Type/ length Flags Time and 19.001 CWU date 8 Byte System time for display on the room thermostat. See parameter P07 (3 or 4) 3 Time of day Time and 10.001 CWU date 3 Byte Another object for receiving the time of day for display on the room thermostat. See parameter P07 (3 or 4) 4 Fault information Alarm 219.001 CT Info 6 Byte Common alarm output.
Obj 27 Object name Function Type/ length Flags Cooling output 0…100% 5.001 CRT primary 8 bit Indicates the position of the cooling actuator of the first stage. E.g. 2-pipe with electric heater application: Output of the cooling coil. 28 Cooling output 0…100% 5.001 CRT secondary 8 bit Indicates the position of the cooling actuator of the second stage. E.g. 2-stage changeover application: Output of the second cooling stage. 29 Enable electric Enable / 1.
3.13 Communication objects (LTE-mode) RDG Geographical zone A.R.S Room operating mode: Time switch (Time switch zone) X.1.1 / X.Y.1 Application mode Room operating mode: Preselection Geographical zone A.R.S X.Y.1 Room temperature output Comfort setpoint Setpoints heating Setpoints cooling Fan speed Setpoint shift heating Setpoint shift cooling Heat distr. zone Heating coil energy demand heating coil Heating/Cooling changeover Ref. distr. zone cooling coil Cooling coil energy demand Heat distr.
3.14 Control parameters A number of control parameters can be readjusted to optimize control performance. This can be done on the thermostat via HMI or via commissioning / operating tool. These parameters can also be set during operation without opening the unit. In the event of a power failure, all control parameter settings are retained.
3.14.2 Parameter setting / download via tool Control parameters can be adjusted via bus either by parameter download during commissioning or during normal operation with a tool like ACS.
Range 2-pipe: 1 = Cooling only 0 = Heating only 1 = Cooling only 2 = H/C changeover manual 3 = H/C changeover auto 4 = Heating and Cooling 1 = Auto – Protection 2 = Auto - Comfort - Economy Protection 0 = Auto - Manual 1 = Manual 2 = Auto - Manual - Protection C = ° Celsius F = ° Fahrenheit – 3 ... 3 K 0 = Room temperature 1 = Setpoint 0 = --- (No display) 1 = °C and °F 2 = Outside temperature (via bus) 3 = Time of day (12h) (via bus) 4 = Time of day (24h) (via bus) 5 ... 40 °C 5 ... 40 °C 5 ...
Range RDG160KN 2K 1K 2K 2K 2K 5 min 45 min 16 °C 28 °C 1: = Ext. sensor 0.5 … 6 K 0.5 … 6 K 0.5 … 6 K 0.5 … 5 K 0.5 … 5 K 0…10 min 0...120 min 10…25 °C 27…40 °C 0 = --- (no function) 1 = Room temp ext.
Range RDG100KN RDG160KN 1...20 min OFF: Not active 1…5 min: Active with selected duration OFF, 10...50 °C 0 = Disabled 1 = Enabled 2 = Heating only 3 = Cooling only 1 = 1-speed 2 = 3-speed 1 = 1-speed fan 2 = 3-speed fan 3 = DC 0...10 V (ECM fan) 0...360 sec 80...100% ECM: fan min…100% 30..75% ECM: 1%...fan max. 1...15% ECM: 1..100% ON: Enabled OFF: Disabled 1...
P81 P82 P83 P84 P85 P86 P88 Range 255 --1 ------0 1…255 ---, 1...126 ---, 1...63 ---, 1...31 ---, 1...31 ---, 1...31 0 = Economy 1 = Comfort Communications Device address 1) Geographical zone (apartment) 2) Geographical zone (room) 2) Heat distr zone heating coil Refrig distr zone cooling coil Heat distr zone heating surface Transformation Precomfort 1) 2) Dependencies Factory setting Appl, P01 Appl, P01 Appl Physical address = Area.Line.DeviceAddress. Factory setting of Area = 0, Line = 2.
4. Handling 4.1 Mounting and installation Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the floor. Mounting • Mount the room thermostat in a clean, dry indoor place without direct airflow from a heating / cooling device, and not exposed to dripping or splash water. Wiring See Mounting Instructions M3191 [3] enclosed with the thermostat.
4.2 Applications Commissioning The room thermostats are delivered with a fixed set of applications. Select and activate the relevant application during commissioning using one of the following tools: – Local DIP switch and HMI – Synco ACS – ETS Set the DIP switches before snapping the thermostat to the mounting plate, if you want to select an application via DIP switches.
Control parameters The thermostat's control parameters can be set to ensure optimum performance of the entire system. The parameters can be adjusted using – Local HMI – Synco ACS – ETS The control parameters of the thermostat can be set to ensure optimum performance of the entire system (see section 3.14, control parameters). Control sequence • The control sequence may need to be set via parameter P01 depending on the application.
4.3 Operation See also Operating Instructions B3191 [2] enclosed with the thermostat. Layout 1 1. Operating mode selector / Esc 2. Fan mode selector / Ok 3. Rotary knob to adjust setpoints and parameters 2 3 Button operation User action Effect, description Normal operation Actual operating mode and state are indicated by symbols. Enter operating mode selection; backlit LCD turns on, all possible mode symbols turn on, indicator element (arrow) will appear on the current mode / state.
Display # Symbol Description # Symbol Description 1 Heating mode 14 Automatic fan 2 Heating mode, electric heater active 15 Manual fan 3 Cooling mode 4 Comfort 5 Economy 6 Auto Timer mode according to schedule (via bus) 17 Degrees Celsius Degrees Fahrenheit 8 Protection mode 18 Digits for room temperature and setpoint display 9 Escape 19 Button lock 10 Additional user information, like outside temperature or time of day from KNX bus.
4.4 Remote operation The RDG thermostats can be operated from a remote location using an OZW772 web server, a RMZ792 bus operating unit or the ACS tool. 4.5 Disposal The devices are considered electronics devices for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic waste. • Dispose of the device via the channels provided for this purpose. • Comply with all local and currently applicable laws and regulations.
5. Supported KNX tools 5.1 ETS ETS is an engineering tool. It can be used for the full commissioning of the RDG KNX thermostats. ETS The following functions can be realized with ETS4: – – – – Define and download the physical address Define and download the application (plant type, control sequence) Set up and download the thermostat's control parameters Set up and download group addresses This basic documentation does not describe how to operate ETS and commission a device.
The control parameters, ([Pxx] description) can also be adjusted and downloaded. Refer to section 3.14. 5.2 ACS ACS tool With the ACS tool, the RDG KNX thermostats can be commissioned (physical address, application, parameters). They can be operated or monitored via bus during normal operation. This Manual does not describe how the physical address is defined. Also, it only gives a brief overview of the main functionality of ACS. For more information, refer to the ACS online help.
The application and control parameters can be adjusted and downloaded. Column Line no. contains the parameter number as shown in the parameter table. Refer to section 3.14, control parameters. STOP Note! Some parameters have a different range in ACS than in the room thermostats. The thermostat does not accept changes that are outside its range. This can be observed online by the fact that a changed value jumps back to the original value.
Parameter settings in ACS Notes: ACS supports parameter settings even during normal operation. To change a control parameter, select Popcard, then Settings. • Make sure you have logged on with sufficient access right.
Plant diagram in ACS ACS offers plant diagrams for easy monitoring and operation of the thermostat. To start this application, select Applications, then Pant diagram.
Plant type Application Configuration Application Configuration 2-pipe and electric heater 2-pipe fan coil unit with electric heater – Control sequence: No impact (P01 = any) – Fan operation: Not disabled (P52 <> 0) Single stage with electric heater – Control sequence: No impact (P01 =any) – Fan operation: Disabled (P52 = 0) 2-pipe and radiator 2-pipe fan coil unit with radiator – Control sequence: No impact (P01 = any) – Fan operation: Not disabled (P52 <> 0) Single stage with radiator – Control seq
Plant type 4-pipe with el heater Application Configuration Application Configuration 4-pipe fan coil unit with electric heater – Control sequence: Not auto c/o (P01 <> 3) – Fan operation: Not disabled (P52 <> 0) 1 stage Heat and Cool with electric heater – Control sequence: No impact (P01 <> 3) – Fan operation: Disabled (P52 = 0) Fan coil unit main / secondary with electric heater – Control sequence: Auto c/o (P01 = 3) – Fan operation: Not disabled (P52 <> 0) Main / secondary with el heater – Control
5.2.3 Operation and monitoring with OZW772 . The OZW772 web server enables users to operate a Synco HVAC system from a remote location – via PC or from a smart phone using the HomeControl app. A start page shows the most important data points. A combination of menu / path navigation enables users to access all data points quickly and straightforwardly. The entire installation can be visualized in the form of plant diagrams.
6. Connection 6.1 Connection terminals L X1 M N Q1 Q2 Q3 X2 SELV 3191A01 RDG100KN D1 GND CE+ CE - Y1 Y2 Y3 Y4 G X1 M X2 SELV 3191A11 RDG160KN G0 L Q1 Q2 Q3 D1 GND Y50 CE+ CE - Y10 Y20 L, N G, G0 L X1, X2 Operating voltage AC 230 V (RDG100KN) Operating voltage AC 24 V (RDG160KN) Feed for relays AC 24...230 V (RDG160KN) Multifunctional input for temperature sensor (e.g. QAH11.
6.2 Connection diagrams RDG100KN Application V1 • 2-pipe YHC • 2-pipe and radiator • 4-pipe • 2-stage • 2-pipe and electric heater YHC YR • 4-pipe and electric heater YH st 1 V2 YC nd 2 YHC E1 YH YC E1 N1 Room thermostat RDG100KN F External circuit breaker S1, S2 Switch (keycard, window contact, presence detector, etc.) S3 Switch at SELV input (keycard, window contact) B1, B2 Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.
RDG160KN DC 0...
N1 Room thermostat RDG160KN F External circuit breaker S1...S3 Switch (keycard, window contact, presence detector, etc.) B1, B2 Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.) CE+ KNX data + CE– KNX data – M1 1- or 3-speed fan, DC 0...10 V fan V1, V2 Valve actuators: On/Off or DC 0...
7. Mechanical design 7.1 General The room thermostat consists of 2 parts: • Plastic housing with electronics, operating elements and room temperature sensor • Mounting plate with the screw terminals The housing engages in the mounting plate and is secured with 2 screws. 1 2 1. Operating mode selector / Esc 2. Fan mode selector / Ok 3. Rotary knob to adjust setpoints and parameters 3 For operation, refer to section 4.3. 7.2 Dimensions Dimensions in mm 4.0 28.3 28.3 9.0 4.0 128.0 28.3 28.
8. Technical data RDG100KN Power supply Caution Outputs Caution STOP Note! Inputs Rated voltage AC 230 V Frequency 50/60 Hz Power consumption Max. 8 VA / 1 W No internal fuse External preliminary protection with max. C 10 A circuit breaker required in all cases Fan control Q1, Q2, Q3 – N AC 230 V, Rating min, max resistive (inductive) 5 mA...5(4) A No internal fuse External preliminary protection with max.
RDG160KN Power supply Caution Outputs STOP Note! Caution Inputs Rated voltage AC 24 V DC 24 V : Make sure to connect G to + and G0 to - DC 24 V Frequency 50/60 Hz Power consumption Max. 2 VA / 2 W No internal fuse External preliminary protection with max. C 10 A circuit breaker required in all cases Q1 / Q2 / Q3 / L - N (relay) AC 24...230 V Use for 3-speed fan control Rating min, max resistive (inductive) 5 mA...
RDG100KN, RDG160KN KNX bus Operational data Interface type KNX, TP1-64 (electrically isolated) Bus current 20 mA Bus topology: See KNX Manual (see 1.2 "Reference documents") Switching differential (adjustable) Heating mode (P30) 2 K (0.5…6 K) Cooling mode (P31) 1 K (0.
2011/65/EU EN50581 Safety class II as per EN60730 Pollution class Normal Degree of protection of housing IP30 as per EN60529 *) The product environmental declaration CE1E3181 contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). Meets the requirements for eu.bac certification See product list at: http://www.eubaccert.eu/licences-by-criteria.
Index 0 0…10 V DC 0…10 V ........................................ 53 1 1- / 3-speed fan..................................................... 53 1-speed fan ........................................................... 55 3 3-position control signal ........................................ 49 3-speed fan ........................................................... 55 A Absence ................................................................ 17 ACS tool ........................................................
Integration via KNX ................................................. 9 K KNX addressing .................................................... 78 KNX Bus power supply ......................................... 77 KNX functions ......................................................... 9 KNX LTE mode ..................................................... 60 KNX overview ................................................... 6, 60 KNX parametersl ..................................................
/ 102 Siemens Building Technologies RDG100KN, RDG160KN Basic documentation Index CE1P3191en 2014-05-23
Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.buildingtechnologies.siemens.