Technical data

Functions
Room temperature control via built-in temperature sensor or external room
temperature / return air temperature sensor
Changeover between heating and cooling mode (automatic via local sensor or
bus, or manual)
Selection of applications via DIP switches or commissioning tool (ACS, ETS)
Select operating mode via operating mode button on the thermostat
Parameters download with commissioning tool (ACS, ETS)
Temporary Comfort mode extension
Single speed, 3-speed or DC 0...10 V fan control (automatic or manual)
Display of current room temperature or setpoint in °C and/or °F
Minimum and maximum limitation of room temperature setpoint
Button lock (automatic or manual)
3 multifunctional inputs, freely selectable for:
Operating mode switchover contact (keycard, window contact, etc.)
Sensor for automatic heating / cooling changeover
External room temperature or return air temperature sensor
Dewpoint sensor
Electric heater enable
Fault input
Monitor input for temperature sensor or switch status
Supply air temperature sensor (RDG160KN)
Advanced fan control function, e.g. fan kick, fan start delay, selectable fan
operation (enable, disable or depending on heating or cooling mode)
Purge function together with 2-port valve in a 2-pipe changeover system
Reminder to clean fan filters
Floor heating temperature limitation
Minimum and maximum supply air temperature limitation (RDG160KN)
Reload factory settings for commissioning and control parameters
KNX bus (terminals CE+ and CE-) for communication with Synco or KNX
compatible devices
Display of outside temperature or time of day via KNX bus
Time scheduling and central control of setpoints via KNX bus
With a Synco RMB7xx controller, the energy demand signal of the thermostat is
used to optimize energy supply
Selectable relay function for switching external equipment (RDG160KN)
3 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23