s Room thermostats with KNX communications 3 191 RDG100KN RDG160KN – For fan coil unit applications – For universal applications – For use with compressor in DX type equipment • • • • • • • • • • • • • • • • KNX bus communication (S-mode and LTE mode) Backlit display 2P / PI / P control Outputs for On/Off, PWM, 3-position or DC 0...10 V control Outputs for 3-speed, 1-speed, or DC (DC 0...10 V) fan 3 multifunctional inputs for keycard contact, external sensor, etc.
Use The RDG1...
Functions • Room temperature control via built-in temperature sensor or external room temperature / return air temperature sensor • Changeover between heating and cooling mode (automatic via local sensor or bus, or manual) • Selection of applications via DIP switches or commissioning tool (ACS, ETS) • Select operating mode via operating mode button on the thermostat • Parameters download with commissioning tool (ACS, ETS) • Temporary Comfort mode extension • Single speed, 3-speed or DC 0...
Applications The thermostats support the following applications, which can be configured using the DIP switches at the rear of the unit or a commissioning tool. DIP switches 1...3 need to be set to OFF (remote configuration, factory setting) to select an application via commissioning tool.
Applications for Universal systems Applications, DIP setting, Control outputs 1 2 3 4 5 D3 T • Chilled / heated ceiling and electric heater B2 ON OFF 1 2 3 4 5 D3 T B2 OFF 1 D3 T T B1 B1 B1 T N1 YR N1 Using RDG100KN, RDG160KN Using RDG100KN, RDG160KN • 2-stage chilled / heated ceiling • Chilled ceiling and radiator ON OFF 2 3 4 3 4 5 T N1 Using RDG100KN, RDG160KN ON OFF 1 5 2 3 4 5 3191S13 1 2 Y1 T YE T ON T Y1 Y1 • Chilled / heated ceiling and ra
Applications for heat pump systems (RDG160KN) Applications, DIP setting, Control outputs ON OFF 2 3 4 5 3181S31 1 • Heated or cooled with compressors, with electric heater D3 ON OFF 1 2 3 4 3 4 5 3181S32 • Heated or cooled with compressors D3 T T B1 B1 YE N1 T T Using RDG160KN • Heated and cooled with compressors ON OFF 2 3 4 5 D3 T Key 2 D3 T T B1 N1 2 5 T N1 Using RDG160KN Control outputs On/Off , DC 0...10 V Y1 Y2 YE OFF B1 Using RDG160KN Product no.
Type summary Product no. RDG100KN RDG160KN Stock no. Features Operating voltage S55770-T163 S55770-T297 AC 230 V AC 24 V Fan Number of control outputs On/Off 1) 3 2) 2 PWM 1) 2 3-pos. 1) 2 DC 2 2 Backlit LCD 3-stage DC 2) 3) 1) Selectable: On/Off, PWM or 3-position (triac outputs) 2) Either On/Off or DC control signal 3) 3-speed fan selectable only with DC outputs Equipment combinations On / off actuators Description Product no.
DC 0…10 V actuators Electrical actuator, DC 0...10 V (for radiator valves) Electrical actuator, DC 0...10 V (for 2- and 3-port valves / V…P45) Electrical actuator, DC 0...10 V (for small valves 2.5 mm) Electrical actuator, DC 0...10 V (for small valves 5.5 mm) Electrical actuator, DC 0...10 V (for CombiValves VPI45) Electromotoric actuator, DC 0...10 V (for valves 5.5 mm) SSA61... 4893 SSC61… 4895 SSP61… 4864 SSB61... 4891 SSD61...
Mechanical design The room thermostat consists of 2 parts: • Plastic housing with electronics, operating elements and room temperature sensor • Mounting plate with the screw terminals The housing engages in the mounting plate and is secured with 2 screws.
Display # Symbol Description # Symbol Description 1 Heating mode 14 Automatic fan 2 Heating mode, electric heater active 15 Manual fan 3 Cooling mode 4 Comfort 5 Economy 6 Auto Timer mode according to schedule (via KNX) 17 Degrees Celsius Degrees Fahrenheit 8 Protection mode 18 Digits for room temperature and setpoint display 9 Escape 19 Button lock 10 Additional user information, like outdoor temperature or time of day from KNX bus.
Engineering notes See the "Reference documentation", page 17 for information on how to engineer the KNX bus (topology, bus repeaters, etc.) and how to select and dimension connecting cables for supply voltage and field devices. Mounting and installation Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the floor.
Commissioning notes Applications The room thermostats are delivered with a fixed set of applications. Select and activate the relevant application during commissioning using one of the following tools: − Local DIP switch and HMI − Synco ACS − ETS Set the DIP switches before snapping the thermostat to the mounting plate, if you want to select an application via DIP switches. All DIP switches need to be set to “OFF” ("remote configuration"), if you want to select an application via commissioning tool.
Control sequence • The control sequence may need to be set via parameter P01 depending on the application. The factory setting is as follows: Application 2-pipe and chilled / heated ceiling, and 2-stage 4-pipe, chilled ceiling and radiator Factory setting P01 1 = Cooling only 4 = Heating and cooling Calibrate sensor • Recalibrate the temperature sensor if the room temperature displayed on the thermostat does not match the room temperature measured (after min. 1 hour of operation).
Technical data RDG100KN Power supply Caution Outputs Caution STOP Note! Inputs Rated voltage AC 230 V Frequency 50/60 Hz Max. 8 VA / 1 W Power consumption No internal fuse External preliminary protection with max. C 10 A circuit breaker required in all cases Fan control Q1, Q2, Q3 – N AC 230 V Rating min, max resistive (inductive) 5 mA...5(4) A No internal fuse External preliminary protection with max.
RDG160KN Power supply Caution Outputs STOP Note! Caution Inputs Rated voltage AC 24 V DC 24 V : Make sure to connect G to + and G0 to - DC 24 V Frequency 50/60 Hz Power consumption Max. 2 VA / 2 W No internal fuse External preliminary protection with max. C 10 A circuit breaker required in all cases Q1 / Q2 / Q3 / L - N (relay) AC 24...230 V Use for 3-speed fan control Rating min, max resistive (inductive) 5 mA...
RDG100KN, RDG160KN KNX bus Operational data Interface type KNX, TP1-64 (electrically isolated) Bus current 20 mA Bus topology: See KNX manual (reference documentation, see below) Switching differential, adjustable Heating mode (P30) 2 K (0.5…6 K) Cooling mode (P31) 1 K (0.
Low-voltage directive Electrical safety 2006/95/EC EN60730–1, EN50491-3 AS/NZS 61000-6-3 2011/65/EU Reduction of hazardous substances EN50581 Safety class II as per EN60730 Pollution class Normal Degree of protection of housing IP30 as per EN60529 *) The product environmental declaration CE1E3181 contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). Meets the requirements for eu.
Connection terminals M X2 L X1 N Q1 Q2 Q3 SELV 3191A01 RDG100KN D1 GND CE+ CE - Y1 Y2 Y3 Y4 G X1 M X2 SELV 3191A11 RDG160KN G0 L Q1 Q2 Q3 D1 GND Y50 CE+ CE - Y10 Y20 L, N G, G0 L X1, X2 Operating voltage AC 230 V (RDG100KN) Operating voltage AC 24 V (RDG160KN) Feed for relays AC 24...230 V (RDG160KN) Multifunctional input for temperature sensor (e.g. QAH11.
Connection diagrams RDG100KN Application V1 • 2-pipe YHC • 2-pipe and radiator • 4-pipe • 2-stage • 2-pipe and electric heater YHC YR YH 1. V2 YC 2. YHC E1 • 4-pipe and electric YH heater E1 YC N1 Room thermostat RDG100KN F External circuit breaker S1, S2 Switch (keycard, window contact, presence detector, etc.) S3 Switch at SELV input (keycard, window contact) B1, B2 Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.
Connection diagrams RDG160KN DC 0...
N1 Room thermostat RDG160KN F External circuit breaker S1...S3 Switch (keycard, window contact, presence detector, etc.) B1, B2 Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.) CE+ KNX data + CE– KNX data – M1 1- or 3-speed fan, DC 0...10 V fan V1, V2 Valve actuators: On/Off or DC 0...