Technical data
76 / 86
Siemens RDG100KN Basic documentation CE1P3191en
Building Technologies Supported KNX tools 22 Jun 2010
ACS Operating offers plant diagrams for easy monitoring and operation of the
thermostat.
To start this application, select Applications, then Pant diagram
ACS provides standard plant diagrams for RDG KNX thermostats, which depend
on the configuration as follows:
Plant type
Application
Configuration
Application
Configuration
2-pipe
2-pipe fan coil unit
– Control sequence: No impact (P01 = any)
– Fan operation: Not disabled (P52 <> 0)
Radiator
– Control sequence: Heating only (P01 = 0)
– Fan operation: Disabled (P52 = 0)
Chilled / heated ceiling
– Control sequence: Changeover (P01 = 2,3)
– Fan operation: Disabled (P52 = 0)
Chilled ceiling
– Control sequence: Cooling only (P01 = 1)
– Fan operation: Disabled (P52 = 0)
Plant diagram in ACS
Operating