Technical data
70 / 86
Siemens RDG100KN Basic documentation CE1P3191en
Building Technologies Handling 22 Jun 2010
4.3 Operation
See also Operating Instructions B3191 [2] enclosed with the thermostat.
1. Operating mode selector / Esc
2. Fan mode selector / Ok
3. Rotary knob to adjust setpoints and
parameters
User action Effect, description
Normal operation Actual operating mode and state are
indicated by symbols
Press any button
(thermostat in normal operation)
Enter operating mode selection;
backlit LCD turns on, all possible mode
symbols turn on, indicator element (arrow)
will appear on the current mode / state
Press left button Change operating mode (indicator element
(arrow) changes to the next mode symbol.
After the last press and a timeout of 3
seconds, the newly selected mode is
confirmed, the other elements disappear.
After a timeout of 20 seconds, the LCD
backlight turns off
Press left button (P01 = 2) Toggle between heating and cooling
Press left button while "Operating
mode" via bus is Economy or while
operating mode switchover contact is
activated
Activate "Extend Comfort mode"
(for details, see page 16)
Keep left button depressed and
turn rotary knob clockwise / counter-
clockwise
Activate timer "Extend presence" / "Extend
absence" and set the time (for details, see
page 16)
Press right button >3 seconds Activate / deactivate button lock
Press right button for fan coil unit Change fan mode
Press right button if P52 = 0 (fan dis-
abled, e.g. in chilled ceiling applica-
tions)
Set thermostat to Protection mode
Turn rotary knob Adjust the room temperature Comfort
setpoint
Press left and right button >3
seconds, release, then press right
button >3 seconds
Enter parameter setting mode “Service
level”
Press left and right button for 3
seconds, release, press left button for
3 seconds, then turn rotary knob
counterclockwise min. ½ revolution
Enter parameter setting mode “Expert level”,
diagnostics and test
Press left and right button simultane-
ously for 6 seconds
Enter (KNX) programming mode