Technical data
69 / 86
Siemens RDG100KN Basic documentation CE1P3191en
Building Technologies Handling 22 Jun 2010
The thermostat's control parameters can be set to ensure optimum performance of
the entire system.
The parameters can be adjusted using
– Local HMI
– Synco ACS
– ETS3 Professional
Parameter and application download with ETS3 will be implemented later.
The control parameters of the thermostat can be set to ensure optimum
performance of the entire system (see section 3.13, control parameters).
The control sequence may need to be set via parameter P01 depending on the
application. The factory setting is as follows:
Application Factory setting P01
2-pipe and chilled / heated ceiling, and 2-stage 1 = cooling only
4-pipe, chilled ceiling and radiator 4 = heating and cooling
Recalibrate the temperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured (after min. 1 hour of
operation). To do this, change parameter P05
We recommend to review the setpoints and setpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy
The programming mode helps identify the thermostat in the KNX network during
commissioning.
Press left and right buttons simultaneously for 6 seconds to activate
programming mode, which is indicated on the display with "PrO
g
".
Programming mode remains active until thermostat identification is complete.
Use ETS3 Professional to assign the KNX group addresses of the thermostat's
communication objects.
Each device has a unique KNX serial number at the rear. An additional sticker with
the same KNX serial number is enclosed in the packaging box. This sticker is
intended for installers for documentation purposes.
Control parameters
Control sequence
Calibrate sensor
Setpoint and range
limitation
Programming mode
Assign KNX group
addresses
KNX serial number