Technical data

66 / 86
Siemens RDG100KN Basic documentation CE1P3191en
Building Technologies Functions 22 Jun 2010
Parameter
Name Range
Diagnostics & test
d01 Application number 0 = (No application)
1 = 2-pipe
2 = 2-pipe with electric heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2-stage heating or cooling
6 = 4-pipe with electric heater
d02 X1 state 0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
d03 X2 state 0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
d04 D1 state 0 = Not activated (for DI)
1 = Activated (DI)
00
= H/C Input shorted
100
= H/C Input open
d05 Test mode for checking the Y1/Y2 actuator's running
direction 3)
"---" = no signal on outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing
d06 Test mode for checking the Y3/Y4 actuator's running
direction 3)
"---" = no signal on outputs Y3 and Y4
OPE = output Y3 forced opening
CLO = output Y4 forced closing
d07 Software version Ux.xx is displayed
3) This parameter can only be quit when the setting is back at “---”.
Press the left button to escape.