Technical data
65 / 86
Siemens RDG100KN Basic documentation CE1P3191en
Building Technologies Functions 22 Jun 2010
Parameter
Name Factory setting Range
Expert level
P53 Fan speeds 3-speed 1 = 1-speed
2 = 3-speed
P54 Fan overrun time 60 sec 0...360 sec
P55 Fan speed switching point high 100% 80...100%
P56 Fan speed switching point med 65% 30..75%
P57 Fan speed switching point low 10% 1...15%
P58 Fan start kick ON ON: Enabled
OFF: Disabled
P59 On time minimum fan 2 min 1...6 min
P60 Periodic fan kick Comfort 0 0…89 min, OFF(90)
P61 Periodic fan kick Eco OFF 0…359 min, OFF(360)
P62 Service filter Off (0) Off, 100…9900 h
P65 Protection heating setpoint 8 °C OFF, 5…WCoolProt;
WCoolProt = 40 °C max
P66 Protection cooling setpoint OFF OFF, WHeatProt… 40;
WHeatProt = 5°C min
P67 Fan start delay 0 s 0...180 s
P68 Temporary Comfort mode 0 (= OFF) 0...360 min
P69 Temporary Comfort setpoint OFF OFF = Disabled
ON = Enabled
P71 Restore factory setting OFF OFF = Disabled
ON = Reload start
“8888” is displayed for 3s during
reload process
Parameter
Name Factory setting Range
Communications
P81 Device address 1) 255 1…255
P82 Geographical zone (apartment) 2) --- ---, 1...126
P83 Geographical zone (room) 2) 1 ---, 1...63
P84 Heat distr zone heating coil --- ---, 1...31
P85 Refrig distr zone cooling coil --- ---, 1...31
P86 Heat distr zone heating surface --- ---, 1...31
P88 Transformation Precomfort 0 0 = Economy
1 = Comfort
P46, P47: Setting to 2-position or 3-position is made with DIP switches 4 and 5
1) Physical address = Area.Line.DeviceAddress. Factory setting of Area = 0, Line = 2.
Can be changed by special management service e.g. from line coupler or via ACS commissioning tool.
2) Type = geographical zone A.R.S. In RDG sub zone = fixed value 1
Note: