Technical data

64 / 86
Siemens RDG100KN Basic documentation CE1P3191en
Building Technologies Functions 22 Jun 2010
3.13.4 Parameters of the "Expert level
with diagnostics and test"
Parameter
Name Factory setting Range
Expert level
P30 Heat P-band Xp / switching diff 2 K 0.5 … 6 K
P31 Cool P-band Xp / switching diff 1 K 0.5 … 6 K
P32 Radiator P-band Xp / swi diff 2 K 0.5 … 6 K
P33 Dead zone Comfort mode 2 K 0.5 … 5 K
P34 Setpoint differential 2 K 0.5 … 5 K
P35 Integral action time Tn 5 min 0…10 min
P36 H/C ch'over swi point cooling 16 °C 10…25 °C
P37 H/C ch'over swi point heating 28 °C 27…40 °C
P38 Input X1 1: = Ext. sensor 0 = --- (no function)
1 = Room temp ext. sensor /
Return air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
8 = Monitor input (Temp)
P39 Normal position input X1 0 (N.O.) 0 = Normally open / Open
1 = Normally closed / Close
P40 Input X2 0 = no function 0 = --- (no function)
1 = Room temp ext. sensor /
Return air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
8 = Monitor input (Temp)
P41 Normal position input X2 0 (N.O.) 0 = Normally open / Open
1 = Normally closed / Close
P42 Input D1 3 = Op mode contact 0 = --- (no function)
2 = H/C changeover (DI)
3 = Operating mode contact (DI)
4 = Dew point sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitor input (Digital)
P43 Normal position input D1 0 (N.O.) 0 = Normally open / Open
1 = Normally closed / Close
P44 Actuator running time Y1/Y2 150 s 20…300 sec
P45 Actuator running time Y3/Y4 150 s 20…300 sec
P46 Output Y1/Y2 ON/OFF (1) 0 = 3-position
1 = 2-position
2 = PWM
P47 Output Y3/Y4 ON/OFF (1) 0 = 3-position
1 = 2-position
2 = PWM
P48 On time minimum 2-pos output 1 min. 1...20 min
P49 Off time minimum 2-pos output 1 min. 1...20 min
P50 Purge time OFF OFF: Not active
1…5 min: Active with selected
duration
P51 Flow temp limit floor heating OFF OFF, 10...50 °C
P52 Fan control 1 0 = Disabled
1 = Enabled
2 = Heating only
3 = Cooling only