Technical data

21 / 86
Siemens RDG100KN Basic documentation CE1P3191en
Building Technologies Functions 22 Jun 2010
The Economy setpoints are accessible at the service level (P11, P12); the
Protection setpoints at the expert level (P65, P66).
3.3.2 Setting and adjusting setpoints
Room temperature setpoints can be
– set during commissioning
– adjusted during runtime
The source can be
– the local HMI
– a tool
– a central control unit
The thermostat stores the setpoints
– in EEPROM in the form of parameters
– in the runtime memory
The table below shows the interrelations:
Setpoint setting Stored in EEPROM
of thermostat
Commissioning
– HMI
– Tool download
Input LTE mode Input S-mode
Comfort basic setpoint
Dead zone Comfort 1)
Setpoints Heating
Setpoints Cooling
Comfort basic setpoint P08 Comfort basic setpoint
P33 Dead zone Comfort 1)
Setpoint Economy Heating
Setpoint Economy Cooling
Setpoints Heating
Setpoints Cooling
P11 Economy Heating
P12 Economy Cooling
Setpoint Protection Heating
Setpoint Protection Cooling
P65 Protection Heating
P66 Protection Cooling
Current runtime
setpoints in
thermostat
Setpoint
adjustment
New current
runtime setpoints
in thermostat
Input LTE mode
2)
Input S-mode
3)
Local ope-
ration 3)
Comfort setpoint Setpoint shift H
Setpoint shift C
Comfort setpoint Rotary knob Comfort setpoint
Economy Heating
Economy Cooling
Setpoint shift H
Setpoint shift C
Economy Heating
Economy Cooling
Protection Heating
Protection Cooling
Protection Heating
Protection Cooling
Effective room operating mode
Current setpoint (used by the thermostat for temperature control)
1) Only required for heating AND cooling applications (see section 3.6.10)
2) L
TE mode: the shift is added to the local shift
3) S-Mode: the last intervention wins, either S-Mode input or local operation
KNX
R
Comfort basic setpoint
Comfort setpoint