Data Sheet for Product

10 / 26
Siemens RDF880KN… A6V11282546_en--_e
Smart Infrastructure Touch Screen Flush-mount Room Thermostats with KNX Communications 2021-02-26
Commissioning notes
Select DIP switch setting is required for RDF880KN.... thermostats.
COMMISSIONING: Download via ETS
1. DIP switch setting
All in OFF positions
2. First power up
Press to turn ON
3. Touch & hold this
icon > 5 s to enter
Programming mode
4. Ready for downloading
address & application
Touch “ON“ to exit
COMMISSIONING: Local via DIP Switches
1. Set application via
DIP switches
DIP switch
positions
APPLICATION
1
2
ON
ON
VRF+FLOOR HEAT
OFF
ON
VRF ONLY
ON
OFF
FLOOR HEAT ONLY
2. Configure basic
control parameters
via Wizard
See Configure Parameters
via Wizard in Wizard function.
After power up, the wizard function guides users to configure the basic parameters
for normal operation according to the table below.
Touch / to advance / return to any parameter;
Touch + / - to select any desired available values.
Before power up
Wizard function