Operating Instructions

6 A6V11439451_----_c
Commissioning: Local via DIP switches
1. Set application via
DIP switches
Refer to
DIP switch
positions
Application
1 2
ON OFF Room unit
OFF OFF Room controller
DIP switch setting applies to
RDF870MB only.
Current factory setting for PM2.5
control with 3 speed on/off fan
application:
· APP= 1: PM2.5 control only
· DISP: Room temp= 1; PM2.5= 1
· SEN1= 3: PM2.5 (AI) μg/m
3
(0…10 V)
· SEN2= 0: no function
· FAN= 3: 3 speed fan
2. Configure basic
control parameters
See Parameters on page
17.