Operating Instructions

A6V11439451_----_c 23
Expert Mode Parameters
Item Description Range Factory
settings
PMP PM2.5 control factor Xp 01000 50
PMI
PM2.5 c
ontrol factor
Tn
0…120
min
45
min
CO2P CO2 control factor Xp 0…2000 100
CO2I
CO
2
control factor
Tn
0…120
min
45
min
PMDB PM2.5 control loop
deadband
0…20 10
CODB CO2 control loop
deadband
0…100 50
OPAF Operating mode settings
after power failure/reset
0: Return to previous
operating mode / user
setting
1: Off
0: Return to
previous
operating
mode / user
setting
FANT Fan minimum on time
(dwell time)
1…6 min 2 min
FSET Reload factory settings 0: OFF = Disable
1: ON = Reload start
“--””---””----” is displayed
while reloading
0: OFF = Disable
SW
Software version
EPAS Engineer mode password 0000…4999 0000
XPAS
Expert mode password
5000…9999
9999
Room controller workflow:
EPAS > XPAS > PMP > PMI > PMDB > CO2P > CO2I > CODB > OPAF > FANT >
FSET > SW > EPAS
RDF870MB Room unit workflow: EPAS > XPAS > SW > EPAS