Operating Instructions

A6V11439451_----_c 19
Item Description Range Factory settings
CO2L
CO2 sensor low range 0…Min. of high range 0
UOCH
VOC sensor high
range
Max. of low range…100 5
UOCL
VOC sensor low
range
0…Min. of high range 0
HUMH
Humidity sensor high
range
Max. of low range…100 100
HUML
Humidity sensor low
range
0…Min. of high range 0
TEMH
Temperature sensor
high range
Max. of low range…100 50
TEML
Temperature sensor
low range
-50…Min. of high range 0
SPMH
PM2.5 setpoint high
range
Max. of low range…500 100
SPML
PM2.5 setpoint low
range
0…Min. of high range 12
SPCH
CO2 setpoint high
range
Max. of low range…2000 1500
SPCL
CO2 setpoint low
range
0…Min. of high range 500
FAN
Fan type selection 1: 1 speed fan (ON/OFF)
3: 3 speed fan
4: 4 speed fan
5: ECM fan
3: 3 speed fan
ECMH
ECM fan output limit
high
Max. of ECML…100 % 80 %
ECML
ECM fan output limit
low
0…Min. of ECMH 30 %
TC
Filter time display 0: Disable 0: Disable