Use
Ventilation control in purifier systems:
Typical applications:
Residential apartments
Commercial buildings
Schools/Universities
Hospitals/Healthcare centers
Local and remote configuration via one of the following:
Local HMI
DIP switch selection: room controller or room unit RDF870MB only
Third-party tool Modbus poll/Modbus scan RDF870MB only
ETS RDF870KN only
Functions
For room controllers
Maintain PM2.5 or CO
2
level or both via controlling a fan of fresh air units or air purifiers
Display of room temperature via built-in temperature sensor or bus
Setpoint adjustment for PM2.5 and CO
2
only
PM2.5 and CO
2
values are received from external sensor or via bus.
CO
2
control has higher priority than PM2.5 control if both controls are available.
For room unit
Display room temperature via built-in sensor in °C
Display outside temperature via bus or outside sensor input in °C
Display PM2.5 via bus or outside sensor input in μg/m
3
Display CO
2
via bus or outside sensor input in ppm
Display VOC via bus or outside sensor input in mg/m
3
or %
Display relative humidity via bus or outside sensor input in % r.h.
Setpoint adjustments for all of the above
Common functionalities
Selection of operating modes
Minimum and maximum setpoint limitation
Fan speed adjustment: Auto, manual (up to 4 speeds)
Reload factory settings for commissioning, engineering mode and control parameters
Mechanical design
The room controller/room unit consists of the following parts:
Front panel with electronics, operating elements and built-in room temperature sensor
Mounting base with power electronics
Mounting frame is an additional part to complete the installation for RDF870…